"Pump start heating circuit pump A1, standby mode"
Setting
Explanations
Only if control unit has been changed to constant tem-
perature mode.
OFF
F7:0
In "Standby mode", the internal circulation pump is
permanently off
... ON
F7:1 to
F7:24
Activation of the internal circulation pump in "Standby
mode" is adjustable from 1 to 24 times per day for 10
min. each time.
Constantly ON
F7:25
In "Standby mode", the internal circulation pump is
permanently on
"Outside temperature limit for cancelling reduced set room temperature"
Setting
Explanations
-5 °C
F8:-5
See chapter "Function description"
Observe parameter "A3".
... °C
F8:+10 to
F8:-60
Temperature limit adjustable from +10 to -60°C
Function disabled
F8:-61
"Outside temperature limit for raising the reduced set room temperature to the standard set room tem-
perature"
Setting
Explanations
-14 °C
F9:-14
See chapter "Function description"
... °C
F9:+10 to
F9:-60
Temperature limit adjustable from +10 to -60°C
"Raising the set boiler water or flow temperature when switching from operation with reduced room tem-
perature to operation with standard room temperature"
Setting
Explanations
20 %
FA:20
See chapter "Function description"
... %
FA:0 to
FA:50
Temperature rise adjustable from 0 to 50 %
"Duration for raising the set boiler water or flow temperature"
Setting
Explanations
60 min
FB:60
See parameter "FA"
See chapter "Function description"
... min
FB:0 to
FB:240
Temperature rise adjustable from 0 to 240 min
Parameter level 2
Heating circuit 1, heating circuit 2, heating…
(cont.)
5778741
Parameter