18
Connections to 230 V~ plugs
fÖ
Power supply
lH
■
Power supply for accessories
■
External demand/blocking
Connections to LV plugs
X3
Plug X3 can be removed to facilitate installation.
!
Outside temperature sensor
?
Flow temperature sensor for low loss header
(accessories)
X4
KM-BUS connection, variable speed heating cir-
cuit pump (if installed)
X21 CO limiter (accessories)
aVG
KM-BUS subscriber (accessories)
To connect several accessories, see page 21.
■
Vitotrol 200-A or 300-A remote control unit
■
Vitocom 100, type GSM
■
Mixer extension kit
■
AM1 extension
■
EA1 extension
■
Wireless base station
■
KM-BUS distributor
Information on connecting accessories
When connecting accessories observe the sep-
arate installation instructions provided with
them.
Outside temperature sensor
!
Fitting location for outside temperature sensor
■
North or north-westerly wall, 2 to 2.5 m above
ground level; in multi storey buildings, in the upper
half of the second floor
■
Not above windows, doors or vents
■
Not immediately below balconies or gutters
■
Never render over.
Outside temperature sensor connection
2-core lead, length max. 35 m with a cross-section of
1.5 mm
2
Installing the boiler
Electrical connections
(cont.)
5778741
Installation