4.2 Connection of battery cables
In order to utilize the full capacity of the product, batteries with sufficient capacity and
battery cables with sufficient cross section should be used. See table.
12/3000
24/3000
48/3000
Recommended battery capacity (Ah)
400–1200
200–700
100–400
Recommended DC fuse
400A
300A
125A
Recommended cross-section (mm
2
)
per + and - connection terminal
0 – 5 m
90
50
35
5 – 10 m
120
90
70
24/5000
48/5000
Recommended battery capacity (Ah)
400–1400
200–800
Recommended DC fuse
400A
200A
Recommended cross-section (mm
2
)
per + and - connection terminal
0 – 5 m*
2x 50 mm
2
1x 70 mm
2
5 -10 m*
2x 90 mm
2
2x 70 mm
2
* ‘2x’ means two positive and two negative cables.
Remark: Internal resistance is the important factor when working with low capacity
batteries. Please consult your supplier or the relevant sections of our book “electricity
on board”, downloadable from our website.
Procedure
Proceed as follows to connect the battery cables:
Use an insulated box spanner in order to avoid shorting the battery.
Avoid shorting the battery cables.
•
Undo the four screws at the front of the enclosure and remove the front panel.
•
Connect the battery cables: see Appendix A.
•
Tighten the nuts well for minimal contact resistance.
Содержание Phoenix Inverter 24/3000
Страница 2: ......
Страница 88: ......
Страница 110: ......
Страница 132: ......
Страница 140: ...8 APPENDIX G Dimensions ANNEXE G Dimensions ANHANG G Maße APÉNDICE G Dimensiones BILAGA G Dimensioner ...
Страница 141: ...9 Dimensions 3k cabinet Dimensions armoire 3k Maße 3k Gehäuse Dimensiones armario 3k Dimensioner 3k skåp ...
Страница 142: ...10 Dimensions 5k cabinet Dimensions armoire 5k Maße 5k Gehäuse Dimensiones armario 5k Dimensioner 5k skåp ...
Страница 143: ......