13
EN
NL
F
R
DE
ES
SE
A
p
p
e
n
d
ix
5.4 Implementing settings with a VE.Net panel
To this end, a VE.Net panel and the VE.Net to VE.Bus converter is required.
With VE.Net you can set all parameters, with the exception of the multi-functional relay
and the VirtualSwitch.
5.5 Configuration with DIP switches
A number of settings can be changed using DIP switches (see appendix A, position I).
Procedure:
•
Turn the Inverter on, preferably unloaded.
•
Set the DIP switches for:
o
AES (Automatic Economy Switch)
o
Inverter voltage
o
Inverter frequency
o
selection of stand-alone, parallel or 3-phase operation.
•
To store the settings after the required values have been set: press the 'Up'
button for 2 seconds (
upper
button to the right of the DIP switches, see
appendix A, position J).
Remarks:
- Dipswitches ds8,ds7 and ds6 are not assigned and should remain off.
- The DIP switch functions are described in 'top to bottom' order. Since the uppermost
DIP switch has the highest number (8), descriptions start with the switch numbered 5.
- In parallel mode or 3-phase mode, not all devices require all settings to be made
(see section 5.5.4).
- For parallel or 3-phase mode, read the whole setting procedure and make a note of
the required DIP switch settings before actually implementing them.
- The ‘down’ button is not used in this procedure and must not be pressed!
Note:
This manual is intended for inverters with firmware number xxxx1xx (with x any
number).
Содержание Phoenix Inverter 24/3000
Страница 2: ......
Страница 88: ......
Страница 110: ......
Страница 132: ......
Страница 140: ...8 APPENDIX G Dimensions ANNEXE G Dimensions ANHANG G Maße APÉNDICE G Dimensiones BILAGA G Dimensioner ...
Страница 141: ...9 Dimensions 3k cabinet Dimensions armoire 3k Maße 3k Gehäuse Dimensiones armario 3k Dimensioner 3k skåp ...
Страница 142: ...10 Dimensions 5k cabinet Dimensions armoire 5k Maße 5k Gehäuse Dimensiones armario 5k Dimensioner 5k skåp ...
Страница 143: ......