background image

I-VICFLEX.AQD-M_4

REV_B

I-VICFLEX.AQD-M 

/ Victaulic

®

 VicFlex

 Style AQD-M Bracket / Installation Instructions

1-INCH/DN25 IGS CONNECTION TO THE 

SPRINKLER PIPING USING A SERIES AH2-CC 

FLEXIBLE HOSE

INCORRECT - Orignal Groove System (OGS) Groove Profile

CORRECT - IGS Groove Profile

Pipe and grooves are not shown to scale

The Style 108 Coupling of the Series AH2-CC shall be used 

ONLY

 

with sprinkler piping connections that are prepared to Victaulic IGS 
proprietary groove specifications. 

DO NOT

 attempt to install the 

coupling on sprinkler piping connections that are prepared to any other 
groove specification. Refer to Victaulic publication 25.14 for the IGS 
groove specification, which can be downloaded at victaulic.com.

 WARNING

•  The flexible hose shall not be bent or fluctuated up-and-down or 

side-to-side when pressurized.

Failure to follow this instruction could cause improper sprinkler 
operation, resulting in death or serious personal injury and property 
damage.

DO NOT REMOVE 

NUT/BOLT/LINKAGE FOR 

INITIAL INSTALLATION

1.  DO NOT DISASSEMBLE THE COUPLING:

 The Style 108 Coupling 

of the Series AH2-CC is designed so that the installer does not 
need to remove the nut, bolt, or linkage for initial installation. This 
facilitates installation by allowing the installer to directly insert the 
sprinkler piping’s grooved end into the coupling.

2. 

The outside surface of the sprinkler piping, between the groove 
and the end of the sprinkler piping, shall be generally free from 
indentations, projections, weld seam anomalies, and roll marks 
to ensure a leak-tight seal. All oil, grease, loose paint, dirt, and 
cutting particles shall be removed.

The sprinkler piping’s outside diameter (“OD”), groove dimensions, 
and maximum allowable flare diameter shall be within the tolerances 
published in current Victaulic IGS specifications, publication 25.14, 
which can be downloaded at victaulic.com.

3. 

Check the gasket to verify that it is suitable for the intended 
service. The color code identifies the material grade. 

Refer to 

Victaulic publication 05.01 for the color code chart, which can 
be downloaded at victaulic.com, and the “NOTICE” below for 
important gasket information.

 CAUTION

•  If any conditions listed in the "NOTICE" below are met, a thin 

coat of a compatible lubricant shall be applied only to the gasket 
sealing lips to help prevent pinching, rolling, or tearing during 
installation.

•  DO NOT use excessive lubricant on the gasket sealing lips.
Failure to use a compatible lubricant may cause gasket damage, 
resulting in joint leakage and property damage.

3a.

  If any conditions listed in the “NOTICE” below are met, apply a 

thin coat of a compatible lubricant, such as Victaulic Lubricant 
or an EPDM-compatible lubricant, only to the gasket sealing lips. 
Silicone grease may be used (silicone spray is not a compatible 
lubricant).

NOTICE

•  Gaskets for Style 108 Coupling assemblies of AH2-CC Flexible 

Hoses are pre-lubricated. Additional lubrication is not required 

for the initial installation of wet pipe systems that are installed 

at or continuously operating above 0°F/–18°C.

Supplemental lubrication is required only if any of the following 

conditions exist. Apply a thin coat of a compatible lubricant to 

the gasket sealing lips, as noted in step 3a on this page. It is 

not necessary to remove the gasket from the housings to apply 

additional lubricant to the gasket sealing lips.
•  If the installation or continuous operating temperature is below 

0°F/–18°C

•  If the gasket has been exposed to fluids prior to installation
•  If the surface of the gasket does not have a hazy appearance
•  If the gasket is being installed into a dry pipe system
•  If the system will be subjected to air tests prior to being filled 

with water

•  If the gasket was involved in a previous installation
Lubricated gaskets will not enhance sealing capabilities on 
adverse sprinkler piping conditions. Sprinkler piping condition 
and preparation shall conform to the requirements listed in these 
product installation instructions.

 WARNING

•  Never leave a Style 108 Coupling of a Series AH2-CC partially 

assembled on grooved sprinkler piping. ALWAYS TIGHTEN THE 
HARDWARE IMMEDIATELY IN ACCORDANCE WITH THESE 
INSTRUCTIONS. A partially  assembled coupling poses a drop or 
fall hazard during installation and a burst hazard during testing.

•  Keep hands away from the grooved sprinkler piping and the 

openings of the coupling when attempting to insert the grooved 
sprinkler piping into the coupling.

•  Keep hands away from coupling openings during tightening.
Failure to follow these instructions could result in death or serious 
personal injury and property damage.

Содержание VicFlex I-VICFLEX.AQD-M

Страница 1: ...product installation It is the system designer s responsibility to verify suitability of stainless steel flexible hose for use with the intended fluid media within the piping system and external environment The material specifier shall evaluate the effect of chemical composition pH level operating temperature chloride level oxygen level and flow rate on stainless steel components to confirm system...

Страница 2: ...rinkler system piping to domestic hot water systems DO NOT allow electrical wiring or other cabling to be hung or wrapped around the sprinkler piping system DO NOT install sprinklers and sprinkler fittings where ambient conditions may fall below or exceed the maximum listed or approved temperature ratings The flexible hose shall not be bent or fluctuated up and down or side to side when pressurize...

Страница 3: ... 1 2 3 4 Item Series AH2 CC Description 1 Flexible Hose Assembly 2 Coupling Assembly 3 Identification Sleeve 4 No 140 Male NPT or BSPT Thread x Groove Adapter Nipple See Note Above BRACKET ASSEMBLY DRAWINGS Refer to pages 7 8 of this manual for bracket installation instructions Style AQD M Bracket 2 4 5 3 1 3 2 4 1 5 Item Style AQD M Description 1 Bracket 2 Sprinkler Reducer 3 Coupling Assembly 4 ...

Страница 4: ...E below are met a thin coat of a compatible lubricant shall be applied only to the gasket sealing lips to help prevent pinching rolling or tearing during installation DO NOT use excessive lubricant on the gasket sealing lips Failure to use a compatible lubricant may cause gasket damage resulting in joint leakage and property damage 3a If any conditions listed in the NOTICE below are met apply a th...

Страница 5: ... Metric nut deep well socket tighten the nut until metal to metal contact occurs at the bolt pads Verify that the oval neck of the bolt seats properly in the bolt hole DO NOT continue to tighten the nut after metal to metal bolt pad contact is achieved If you suspect that any hardware has been over tightened as indicated by a bend in the bolt bulging of the nut at the bolt pad interface or damage ...

Страница 6: ... 5 Insert the inlet end of the Series AH2 CC Flexible Hose into the No 101 90 Elbow or No 102 Straight Tee Verify that the gasket is seated fully in the gasket pocket of each housing and that the housings keys engage with the spacer on the inlet end of the Series AH2 CC Flexible Hose 5a Reinstall the two bolts and nuts that were removed in step 4 NOTE Verify that the oval neck of each bolt seats p...

Страница 7: ...n Connect the nut to the sprinkler reducer DO NOT use pipe joint compound or PTFE thread sealant tape on the fine threads The seal inside the nut of the flexible hose provides the leak proof connection Tighten the connection nut to a torque of 40ft lbs 54N m approximately 1 2 to 3 4 of a turn past hand tight NOTE To prevent damage to the seal tighten the assembly by applying torque only to the con...

Страница 8: ...racket as a template drill a 3 16 hole at each location 4a Install a 3 16 stainless steel domed head sealing blind rivet recommended into each drilled hole NOTE Hardware is not included and shall be stainless steel or a material suitable for the application 4b Four stainless steel 10 Type AB self tapping metal screws can be used instead of rivets When using self tapping sheet metal screws holes do...

Страница 9: ...on of the I 109 installation instructions 5a For applications where a Style 005 FireLock Rigid Coupling with silicone gasket is required refer to the current version of the I 100 Field Installation Handbook for instructions For silicone gaskets use Victaulic Lubricant or a silicone compatible lubricant DO NOT use silicone lubricant on silicone gaskets 6 Apply the duct mastic sealant to cover over ...

Страница 10: ...The sprinkler piping s outside diameter OD groove dimensions and maximum allowable flare diameter shall be within the tolerances published in current Victaulic IGS specifications publication 25 14 which can be downloaded at victaulic com Spacer Inspect Inlet End of Flexible Hose 5 Inspect the end of the Series AH2 CC Flexible Hose to verify that there is no damage dents crushed edges etc A new Vic...

Страница 11: ...mm Outlet Size inches Metric Equivalent Length of 1 inch DN25 Schedule 40 Pipe feet meters Maximum Number of 90 Bends AH2 CC 48 48 1220 1 2 DN15 23 4 3 7 1 7 inch 178 mm minimum bend radius tested with standard 53 4 inch 146 mm length straight reducer A higher number of bends may be permitted provided the sum of degrees is equal to or less than the total maximum allowable degrees of bends e g Two ...

Страница 12: ...M Bracket For complete contact information visit victaulic com I VICFLEX AQD M 14906 REV B UPDATED 07 2020 Z000AQDM00 VICTAULIC AND VICFLEX ARE REGISTERED TRADEMARKS OR TRADEMARKS OF VICTAULIC COMPANY AND OR ITS AFFILIATED ENTITIES IN THE UNITED STATES AND OR OTHER COUNTRIES 2020 VICTAULIC COMPANY ALL RIGHTS RESERVED ...

Отзывы: