background image

I-VICFLEX.AQD-M_5

REV_B

I-VICFLEX.AQD-M 

/ Victaulic

®

 VicFlex

 Styles AQD-M Bracket / Installation Instructions

4. 

Assemble the joint by 
inserting the grooved end of 
the sprinkler piping into the 
opening of the coupling. The 
grooved sprinkler piping shall 
be inserted into the coupling 
until contact with the center 
leg of the gasket occurs. A 
visual check is required to 
verify that the coupling keys 
align with the groove in the 
sprinkler piping and engage 
with the spacer on the inlet 
end of the flexible hose.

 WARNING

•  The nut shall be tightened until metal-to-metal contact occurs at 

the bolt pads, as indicated in steps 5 and 6.

•  DO NOT overtighten coupling hardware.
Failure to follow instructions for tightening hardware could result in:
•  Personal injury or death
•  Bolt damage or fracture
•  Damaged or broken bolt pads or coupling fractures
•  Joint leakage and property damage
•  A negative impact on system integrity

GOOD

OVAL NECK OF BOLT 

SEATED PROPERLY

BAD

OVAL NECK OF BOLT 

NOT SEATED PROPERLY

5. 

Using an impact tool or a standard socket wrench with an 

11/16

-inch (for Imperial nut)/17-mm (for Metric nut) deep well 

socket, tighten the nut until metal-to-metal contact occurs at the 
bolt pads. Verify that the oval neck of the bolt seats properly in the 
bolt hole. DO NOT continue to tighten the nut after metal-to-metal 
bolt pad contact is achieved. 

If you suspect that any hardware 

has been over-tightened (as indicated by a bend in the bolt, 
bulging of the nut at the bolt pad interface, or damage to the 
bolt pad, etc.), the entire coupling assembly shall be replaced 
immediately.

 

NOTE:

 During tightening, support the hose near the 

Style 108 Coupling to verify that the inlet end of the Series AH2-CC 
Flexible Hose remains straight and aligned with the coupling.

 WARNING

•  Visual inspection of each joint is required.
•  Improperly assembled joints shall be corrected before the 

system is tested or placed into service.

•  Any components that exhibit physical damage due to improper 

assembly shall be replaced before the system is tested or placed 
into service.

Failure to follow these instructions could cause joint failure, 
resulting in death or serious personal injury and property damage.

GOOD

BAD

6.  Visually inspect the bolt pads at each joint to verify that metal-

to-metal contact is achieved, in accordance with step 5.

NOTICE

•  Refer to the instructions on page 10 for reassembly 

requirements.

Содержание VicFlex I-VICFLEX.AQD-M

Страница 1: ...product installation It is the system designer s responsibility to verify suitability of stainless steel flexible hose for use with the intended fluid media within the piping system and external environment The material specifier shall evaluate the effect of chemical composition pH level operating temperature chloride level oxygen level and flow rate on stainless steel components to confirm system...

Страница 2: ...rinkler system piping to domestic hot water systems DO NOT allow electrical wiring or other cabling to be hung or wrapped around the sprinkler piping system DO NOT install sprinklers and sprinkler fittings where ambient conditions may fall below or exceed the maximum listed or approved temperature ratings The flexible hose shall not be bent or fluctuated up and down or side to side when pressurize...

Страница 3: ... 1 2 3 4 Item Series AH2 CC Description 1 Flexible Hose Assembly 2 Coupling Assembly 3 Identification Sleeve 4 No 140 Male NPT or BSPT Thread x Groove Adapter Nipple See Note Above BRACKET ASSEMBLY DRAWINGS Refer to pages 7 8 of this manual for bracket installation instructions Style AQD M Bracket 2 4 5 3 1 3 2 4 1 5 Item Style AQD M Description 1 Bracket 2 Sprinkler Reducer 3 Coupling Assembly 4 ...

Страница 4: ...E below are met a thin coat of a compatible lubricant shall be applied only to the gasket sealing lips to help prevent pinching rolling or tearing during installation DO NOT use excessive lubricant on the gasket sealing lips Failure to use a compatible lubricant may cause gasket damage resulting in joint leakage and property damage 3a If any conditions listed in the NOTICE below are met apply a th...

Страница 5: ... Metric nut deep well socket tighten the nut until metal to metal contact occurs at the bolt pads Verify that the oval neck of the bolt seats properly in the bolt hole DO NOT continue to tighten the nut after metal to metal bolt pad contact is achieved If you suspect that any hardware has been over tightened as indicated by a bend in the bolt bulging of the nut at the bolt pad interface or damage ...

Страница 6: ... 5 Insert the inlet end of the Series AH2 CC Flexible Hose into the No 101 90 Elbow or No 102 Straight Tee Verify that the gasket is seated fully in the gasket pocket of each housing and that the housings keys engage with the spacer on the inlet end of the Series AH2 CC Flexible Hose 5a Reinstall the two bolts and nuts that were removed in step 4 NOTE Verify that the oval neck of each bolt seats p...

Страница 7: ...n Connect the nut to the sprinkler reducer DO NOT use pipe joint compound or PTFE thread sealant tape on the fine threads The seal inside the nut of the flexible hose provides the leak proof connection Tighten the connection nut to a torque of 40ft lbs 54N m approximately 1 2 to 3 4 of a turn past hand tight NOTE To prevent damage to the seal tighten the assembly by applying torque only to the con...

Страница 8: ...racket as a template drill a 3 16 hole at each location 4a Install a 3 16 stainless steel domed head sealing blind rivet recommended into each drilled hole NOTE Hardware is not included and shall be stainless steel or a material suitable for the application 4b Four stainless steel 10 Type AB self tapping metal screws can be used instead of rivets When using self tapping sheet metal screws holes do...

Страница 9: ...on of the I 109 installation instructions 5a For applications where a Style 005 FireLock Rigid Coupling with silicone gasket is required refer to the current version of the I 100 Field Installation Handbook for instructions For silicone gaskets use Victaulic Lubricant or a silicone compatible lubricant DO NOT use silicone lubricant on silicone gaskets 6 Apply the duct mastic sealant to cover over ...

Страница 10: ...The sprinkler piping s outside diameter OD groove dimensions and maximum allowable flare diameter shall be within the tolerances published in current Victaulic IGS specifications publication 25 14 which can be downloaded at victaulic com Spacer Inspect Inlet End of Flexible Hose 5 Inspect the end of the Series AH2 CC Flexible Hose to verify that there is no damage dents crushed edges etc A new Vic...

Страница 11: ...mm Outlet Size inches Metric Equivalent Length of 1 inch DN25 Schedule 40 Pipe feet meters Maximum Number of 90 Bends AH2 CC 48 48 1220 1 2 DN15 23 4 3 7 1 7 inch 178 mm minimum bend radius tested with standard 53 4 inch 146 mm length straight reducer A higher number of bends may be permitted provided the sum of degrees is equal to or less than the total maximum allowable degrees of bends e g Two ...

Страница 12: ...M Bracket For complete contact information visit victaulic com I VICFLEX AQD M 14906 REV B UPDATED 07 2020 Z000AQDM00 VICTAULIC AND VICFLEX ARE REGISTERED TRADEMARKS OR TRADEMARKS OF VICTAULIC COMPANY AND OR ITS AFFILIATED ENTITIES IN THE UNITED STATES AND OR OTHER COUNTRIES 2020 VICTAULIC COMPANY ALL RIGHTS RESERVED ...

Отзывы: