background image

I-VICFLEX.AQD-M_10

REV_B

I-VICFLEX.AQD-M 

/ Victaulic

®

 VicFlex

 Style AQD-M Bracket / Installation Instructions

INSTRUCTIONS FOR REASSEMBLY OF A SERIES 

AH2-CC FLEXIBLE HOSE

 WARNING

•  Always verify that the piping system has 

been completely depressurized and drained 
immediately prior to installation, removal, 
adjustment, or maintenance of any Victaulic 
products.

•  Confirm that any equipment, branch lines, or sections of piping 

that may have been isolated for/during testing or due to valve 
closures/positioning are identified, depressurized, and drained 
immediately prior to installation, removal, adjustment, or 
maintenance of any Victaulic products.

Failure to follow this instruction could result in death or serious 
personal injury and property damage.

1.

  Verify that the system is depressurized and drained completely 

before attempting to remove a Series AH2-CC Flexible Hose from 
the sprinkler piping.

2.

  While supporting the Style 108 Coupling, loosen the nut until 

backed off no further than flush with the end of the bolt. Carefully 
remove the flexible hose/coupling assembly from the sprinkler 
piping.

3.

  Fully disassemble the Style 108 Coupling from the inlet end of the 

Series AH2-CC Flexible Hose by removing the nut, bolt, gasket, 
and linkage from the housings. Inspect all components for any 
damage or wear. If any damage or wear is present, use a new 
Victaulic-supplied coupling assembly.

4. 

Verify that the outside surface of the sprinkler piping, between the 
groove and the end of the sprinkler piping, is generally free from 
indentations, projections, weld seam anomalies, and roll marks 
to ensure a leak-tight seal. All oil, grease, loose paint, dirt, and 
cutting particles shall be removed.

 

The sprinkler piping’s outside diameter (“OD”), groove 
dimensions, and maximum allowable flare diameter shall 
be within the tolerances published in current Victaulic IGS 
specifications, publication 25.14, which can be downloaded at 
victaulic.com.

Spacer

Inspect

Inlet End

of Flexible Hose

5. 

Inspect the end of the Series AH2-CC Flexible Hose to verify that 
there is no damage (dents, crushed edges, etc.). A new, Victaulic-
supplied Series AH2-CC Flexible Hose shall be used if any damage 
is present.

6. 

Verify that the spacer is oriented on the inlet end of the Series 
AH2-CC Flexible Hose, as shown above.

 CAUTION

•  A thin coat of a compatible lubricant shall be used to help 

prevent the gasket from pinching, rolling, or tearing during 
reassembly.

•  DO NOT use excessive lubricant on the gasket sealing lips and 

exterior.

Failure to use a compatible lubricant may cause gasket damage, 
resulting in joint leakage and property damage.

7. 

Apply a thin coat of a compatible lubricant, such as Victaulic 
Lubricant or an EPDM-compatible lubricant, to the gasket sealing 
lips and exterior. Silicone grease may be used (silicone spray is not 
a compatible lubricant). It is normal for the gasket to have a hazy 
white appearance after it has been in service.

8. 

Place the lubricated gasket 
onto the inlet end of the 
flexible hose, then place the 
Style 108 Coupling housings 
over the gasket. Verify that 
the gasket is seated fully 
in the gasket pocket of 
each housing and that the 
housings' keys engage with 
the spacer.

9. 

Install the linkage onto the 
housings, as shown to the 
left.

10. 

Install the bolt, and thread a 
nut onto the bolt. 

NOTE:

 Verify that the oval 

neck of the bolt seats 
properly in the bolt hole. 
DO NOT tighten the nut 
completely. The bolt pads 
need to be set at a gap for 
reinstallation of the coupling. 
The nut should be flush with 
the top of the bolt to provide 
the proper gap.

11.

  Follow all steps on page 5.

Содержание VicFlex I-VICFLEX.AQD-M

Страница 1: ...product installation It is the system designer s responsibility to verify suitability of stainless steel flexible hose for use with the intended fluid media within the piping system and external environment The material specifier shall evaluate the effect of chemical composition pH level operating temperature chloride level oxygen level and flow rate on stainless steel components to confirm system...

Страница 2: ...rinkler system piping to domestic hot water systems DO NOT allow electrical wiring or other cabling to be hung or wrapped around the sprinkler piping system DO NOT install sprinklers and sprinkler fittings where ambient conditions may fall below or exceed the maximum listed or approved temperature ratings The flexible hose shall not be bent or fluctuated up and down or side to side when pressurize...

Страница 3: ... 1 2 3 4 Item Series AH2 CC Description 1 Flexible Hose Assembly 2 Coupling Assembly 3 Identification Sleeve 4 No 140 Male NPT or BSPT Thread x Groove Adapter Nipple See Note Above BRACKET ASSEMBLY DRAWINGS Refer to pages 7 8 of this manual for bracket installation instructions Style AQD M Bracket 2 4 5 3 1 3 2 4 1 5 Item Style AQD M Description 1 Bracket 2 Sprinkler Reducer 3 Coupling Assembly 4 ...

Страница 4: ...E below are met a thin coat of a compatible lubricant shall be applied only to the gasket sealing lips to help prevent pinching rolling or tearing during installation DO NOT use excessive lubricant on the gasket sealing lips Failure to use a compatible lubricant may cause gasket damage resulting in joint leakage and property damage 3a If any conditions listed in the NOTICE below are met apply a th...

Страница 5: ... Metric nut deep well socket tighten the nut until metal to metal contact occurs at the bolt pads Verify that the oval neck of the bolt seats properly in the bolt hole DO NOT continue to tighten the nut after metal to metal bolt pad contact is achieved If you suspect that any hardware has been over tightened as indicated by a bend in the bolt bulging of the nut at the bolt pad interface or damage ...

Страница 6: ... 5 Insert the inlet end of the Series AH2 CC Flexible Hose into the No 101 90 Elbow or No 102 Straight Tee Verify that the gasket is seated fully in the gasket pocket of each housing and that the housings keys engage with the spacer on the inlet end of the Series AH2 CC Flexible Hose 5a Reinstall the two bolts and nuts that were removed in step 4 NOTE Verify that the oval neck of each bolt seats p...

Страница 7: ...n Connect the nut to the sprinkler reducer DO NOT use pipe joint compound or PTFE thread sealant tape on the fine threads The seal inside the nut of the flexible hose provides the leak proof connection Tighten the connection nut to a torque of 40ft lbs 54N m approximately 1 2 to 3 4 of a turn past hand tight NOTE To prevent damage to the seal tighten the assembly by applying torque only to the con...

Страница 8: ...racket as a template drill a 3 16 hole at each location 4a Install a 3 16 stainless steel domed head sealing blind rivet recommended into each drilled hole NOTE Hardware is not included and shall be stainless steel or a material suitable for the application 4b Four stainless steel 10 Type AB self tapping metal screws can be used instead of rivets When using self tapping sheet metal screws holes do...

Страница 9: ...on of the I 109 installation instructions 5a For applications where a Style 005 FireLock Rigid Coupling with silicone gasket is required refer to the current version of the I 100 Field Installation Handbook for instructions For silicone gaskets use Victaulic Lubricant or a silicone compatible lubricant DO NOT use silicone lubricant on silicone gaskets 6 Apply the duct mastic sealant to cover over ...

Страница 10: ...The sprinkler piping s outside diameter OD groove dimensions and maximum allowable flare diameter shall be within the tolerances published in current Victaulic IGS specifications publication 25 14 which can be downloaded at victaulic com Spacer Inspect Inlet End of Flexible Hose 5 Inspect the end of the Series AH2 CC Flexible Hose to verify that there is no damage dents crushed edges etc A new Vic...

Страница 11: ...mm Outlet Size inches Metric Equivalent Length of 1 inch DN25 Schedule 40 Pipe feet meters Maximum Number of 90 Bends AH2 CC 48 48 1220 1 2 DN15 23 4 3 7 1 7 inch 178 mm minimum bend radius tested with standard 53 4 inch 146 mm length straight reducer A higher number of bends may be permitted provided the sum of degrees is equal to or less than the total maximum allowable degrees of bends e g Two ...

Страница 12: ...M Bracket For complete contact information visit victaulic com I VICFLEX AQD M 14906 REV B UPDATED 07 2020 Z000AQDM00 VICTAULIC AND VICFLEX ARE REGISTERED TRADEMARKS OR TRADEMARKS OF VICTAULIC COMPANY AND OR ITS AFFILIATED ENTITIES IN THE UNITED STATES AND OR OTHER COUNTRIES 2020 VICTAULIC COMPANY ALL RIGHTS RESERVED ...

Отзывы: