CONNECTION TO THE SPRINKLER PIPING USING THE SUPPLIED NO. 140 MALE NPT OR BSPT 

THREAD X GROOVE ADAPTER

 WARNING

•  The flexible hose shall not be bent or fluctuated up-and-down or side-to-side when pressurized.
Failure to follow this instruction could cause improper sprinkler operation, resulting in death or serious personal injury and property damage.

1.

  Apply pipe joint compound or PTFE thread sealant tape to the tapered threads of the No. 140 Male NPT or BSPT Thread x Groove Adapter, in 

accordance with the pipe joint compound or tape manufacturer’s instructions. Using a pipe wrench, tighten the adapter into the sprinkler piping.

2.

  Follow all applicable instructions on pages 4 – 6 to make the 1-inch/DN25 IGS connection of the Series AH2-CC Flexible Hose.

INSTALLATION OF THE SPRINKLER REDUCER ONTO THE FLEXIBLE HOSE

1.

  Confirm that the seal inside the nut of the flexible hose is in place 

and is free from damage prior to installation. Connect the nut to the 
sprinkler reducer. 

• 

DO NOT use pipe joint compound or PTFE thread sealant tape on the 
fine threads. The seal inside the nut of the flexible hose provides the 
leak-proof connection.

• 

Tighten the connection nut to a torque of 40 ft-lbs/54 N•m 
(approximately 1/2 to 3/4 of a turn past hand-tight). 

NOTE:

 To prevent 

damage to the seal, tighten the assembly by applying torque only to the 
connection nut and DO NOT exceed the specified torque.

INSTALLING THE STYLE AQD-M BRACKET ONTO THE DUCT

 WARNING

•  Wear a particle mask and protective gloves during preparation of the duct.
•  Wear safety glasses, hardhat, and foot  protection.
Failure to follow these instructions could result in serious respiratory system illness or other personal injury.

NOTE

: Before performing the following steps, determine the location on the duct where the Style AQD-M Bracket will be installed. The location shall 

permit easy access to the Style AQD-M Bracket for inspection purposes. Wear a particle mask, safety glasses, hardhat, and foot protection during this 
phase of installation.

1.

 Drill a 1 1/2-inch/38-mm hole into the surface of the duct at the desired location.

1a.

 Remove all burrs from the hole. 

1b. 

Remove all cutting particles from the surface of the duct.

Содержание VicFlex I-VICFLEX.AQD-M

Страница 1: ...product installation It is the system designer s responsibility to verify suitability of stainless steel flexible hose for use with the intended fluid media within the piping system and external environment The material specifier shall evaluate the effect of chemical composition pH level operating temperature chloride level oxygen level and flow rate on stainless steel components to confirm system...

Страница 2: ...rinkler system piping to domestic hot water systems DO NOT allow electrical wiring or other cabling to be hung or wrapped around the sprinkler piping system DO NOT install sprinklers and sprinkler fittings where ambient conditions may fall below or exceed the maximum listed or approved temperature ratings The flexible hose shall not be bent or fluctuated up and down or side to side when pressurize...

Страница 3: ... 1 2 3 4 Item Series AH2 CC Description 1 Flexible Hose Assembly 2 Coupling Assembly 3 Identification Sleeve 4 No 140 Male NPT or BSPT Thread x Groove Adapter Nipple See Note Above BRACKET ASSEMBLY DRAWINGS Refer to pages 7 8 of this manual for bracket installation instructions Style AQD M Bracket 2 4 5 3 1 3 2 4 1 5 Item Style AQD M Description 1 Bracket 2 Sprinkler Reducer 3 Coupling Assembly 4 ...

Страница 4: ...E below are met a thin coat of a compatible lubricant shall be applied only to the gasket sealing lips to help prevent pinching rolling or tearing during installation DO NOT use excessive lubricant on the gasket sealing lips Failure to use a compatible lubricant may cause gasket damage resulting in joint leakage and property damage 3a If any conditions listed in the NOTICE below are met apply a th...

Страница 5: ... Metric nut deep well socket tighten the nut until metal to metal contact occurs at the bolt pads Verify that the oval neck of the bolt seats properly in the bolt hole DO NOT continue to tighten the nut after metal to metal bolt pad contact is achieved If you suspect that any hardware has been over tightened as indicated by a bend in the bolt bulging of the nut at the bolt pad interface or damage ...

Страница 6: ... 5 Insert the inlet end of the Series AH2 CC Flexible Hose into the No 101 90 Elbow or No 102 Straight Tee Verify that the gasket is seated fully in the gasket pocket of each housing and that the housings keys engage with the spacer on the inlet end of the Series AH2 CC Flexible Hose 5a Reinstall the two bolts and nuts that were removed in step 4 NOTE Verify that the oval neck of each bolt seats p...

Страница 7: ...n Connect the nut to the sprinkler reducer DO NOT use pipe joint compound or PTFE thread sealant tape on the fine threads The seal inside the nut of the flexible hose provides the leak proof connection Tighten the connection nut to a torque of 40ft lbs 54N m approximately 1 2 to 3 4 of a turn past hand tight NOTE To prevent damage to the seal tighten the assembly by applying torque only to the con...

Страница 8: ...racket as a template drill a 3 16 hole at each location 4a Install a 3 16 stainless steel domed head sealing blind rivet recommended into each drilled hole NOTE Hardware is not included and shall be stainless steel or a material suitable for the application 4b Four stainless steel 10 Type AB self tapping metal screws can be used instead of rivets When using self tapping sheet metal screws holes do...

Страница 9: ...on of the I 109 installation instructions 5a For applications where a Style 005 FireLock Rigid Coupling with silicone gasket is required refer to the current version of the I 100 Field Installation Handbook for instructions For silicone gaskets use Victaulic Lubricant or a silicone compatible lubricant DO NOT use silicone lubricant on silicone gaskets 6 Apply the duct mastic sealant to cover over ...

Страница 10: ...The sprinkler piping s outside diameter OD groove dimensions and maximum allowable flare diameter shall be within the tolerances published in current Victaulic IGS specifications publication 25 14 which can be downloaded at victaulic com Spacer Inspect Inlet End of Flexible Hose 5 Inspect the end of the Series AH2 CC Flexible Hose to verify that there is no damage dents crushed edges etc A new Vic...

Страница 11: ...mm Outlet Size inches Metric Equivalent Length of 1 inch DN25 Schedule 40 Pipe feet meters Maximum Number of 90 Bends AH2 CC 48 48 1220 1 2 DN15 23 4 3 7 1 7 inch 178 mm minimum bend radius tested with standard 53 4 inch 146 mm length straight reducer A higher number of bends may be permitted provided the sum of degrees is equal to or less than the total maximum allowable degrees of bends e g Two ...

Страница 12: ...M Bracket For complete contact information visit victaulic com I VICFLEX AQD M 14906 REV B UPDATED 07 2020 Z000AQDM00 VICTAULIC AND VICFLEX ARE REGISTERED TRADEMARKS OR TRADEMARKS OF VICTAULIC COMPANY AND OR ITS AFFILIATED ENTITIES IN THE UNITED STATES AND OR OTHER COUNTRIES 2020 VICTAULIC COMPANY ALL RIGHTS RESERVED ...

Отзывы: