25
Viconics Technologies Inc.
www.viconics.com
028-0444-06
November 2018
VTR83X0A5X00B WITH VC3500E5000 RELAY: HEATING/COOLING 4-PIPE FAN COIL UNIT WITH 3-SPEED
FAN AND 2-POSITION VALVES
Configuration
Parameter Name
Configuration Settings
Fan control
3 speed
Fan menu
L-M-H-A
Fan cont. heat
On
BI1
Motion NO or Motion NC (remote PIR sensor only)
BI2
Door Dry
Pipe No
4
Seq. Operat
Ht-Cl
VC3500E5000
2 POSITION
COOLING VALVE
Cooling Coil
2 POSITION
HEATING VALVE
Heating Coil
Door Switch
SED-DOR-P-5045
Airflow Direction
3 Speed Fan
VTR83X0
* Wired remote sensor cannot be used at the same time as wireless remote sensor(s).
Onboard
PIR Sensor
AND / OR
OR*
Wired Remote
PIR Sensor
Wireless Remote
PIR Sensor
Содержание VT8300 Series