Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
Cooling valve opens to maintain room temperature. Heating valve closed.
On Call for Heat
Heating valve opens to maintain room temperature. Cooling valve closed.
Wireless Door Switch
Wireless door switch automatically toggles occupancy.