Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and
heating.
Stand-by Mode (only available when PIR motion detector
sensor is used)
Setpoints revert to those defined by stand-by cooling and
heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and
cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by
“ToccTime” parameter.
On Call for Cool
If supply water temperature is less than 24°C (75F), valve opens
to maintain room temperature, else valve closes.
On Call for Heat
If supply water temperature is greater than 25°C (77F), valve
opens to maintain room temperature, else the valve closes.
Supply Air Sensor
Only used for monitoring. Shows automatically if sensor is
connected.
Wireless Window Switch
Wireless window switch automatically locks out heating/cooling
when window is opened.