APPENDIX C - SCHEMATIC OF CONTROLLERS OCCUPANCY SEQUENCE OF OPERATION WITHOUT DOOR
SENSOR
Setpoints
Time
Unoccupied cool
Occupied cool
Stand-by cool
72°F
76°F
80°F
Movement detected
-
Stand-by timer reset
Into Stand-by mode
-
Unoccupied timer reset
Stand-by
time
Unoccupied
time
Into Unoccupied
mode
Next movement
detected
70°F
62°F
Unoccupied heat
Occupied heat
Stand-by heat
72°F
66°F
70°F
Deadband
Deadband
Deadband
22°C
24.5°C
26.5°C
22°C
21°C
21°C
19°C
16.5°C