53
Viconics Technologies Inc.
www.viconics.com
028-0444-06
November 2018
1 2 3 4 5 6
13 14 15 16 17 18
7 8 9 10 11 12
19 20 21 22 23 24
1 2 3 4 5 6
13 14 15 16 17 18
7 8 9 10 11 12
19 20 21 22 23 24
VT8350
BO2 - F
an L
BO3 - F
an M
BO4 - F
an H
R
C (24 V
ac)
C (Common)
RH
BO8 - A
ux Hea
t
UO9
- NC Cool V
UO10
- NC Hea
t V
UO11
- NO Cool V
UO12
- NO Hea
t V
B
A
Cnet +
B
A
Cnet -
B
A
Cnet REF
UI 16
UI 17
Common
UI 19
UI 20 - RS
Common
UI22 - SS
On / Off C 3 Speed Fan
or
or
HEATING VALVE
IF NC IF NO Com.
COOLING VALVE
IF NC IF NO Com.
COMM ON
24 VAC
FAN HI
FAN MED
FAN LO
FCU Low-voltage
TERMINAL BLOCK
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
Cooling valve opens to maintain room temperature. Heating valve closes. Dehumidification enable
d.
On Call for Heat
Heating valve opens to maintain room temperature. Cooling valve closes. Dehumidification disabled.
On Demand for Dehumidification
Dehumidification is achieved via cooling coil using heating coil for reheat if necessary.
Dehumidification only allowed in COOL mode, or if cooling is enabled in AUTO mode.
Dehumidification disabled if room temperature falls below low ambient lockout temperature, which is cooling setpoint minus
configuration defined deadband value.
Reheat disabled if cooling demand reaches 100%.
Содержание VT8300 Series
Страница 1: ...Fan Coil Unit Application Guide VTR8300 VT8300 Series Room Controllers For firmware Release 2 1 ...
Страница 8: ...VTR83 3 Speed ...
Страница 27: ...VTR83 ECM ...
Страница 44: ...VT83 3 Speed ...
Страница 63: ...VT83 ECM ...
Страница 83: ...VT83 MIX VOLTAGE ...