Figure 21
Customer Interface Board
Installing the Cables
WARNING:
Disable the 24 VAC power to
prevent installer injury and
damage to the unit.
1. Route all cables into the top of the Mini
Dome through the electrical Conduit/Cable
Access Cap, Vicon mount or 1.5-inch Pipe.
Pull approximately 10 ft (3 m) of cable
through the Housing to allow convenient
wiring on a workbench.
2. Route all cables through the Customer
Interface Board’s Cable Clamp.
3. Remove terminal blocks TB1, TB2, TB3 and
TB4 from the Customer Interface Board by
pulling each straight out.
4. Strip approximately 8 inches (20 cm) of
jacket off each Control cable. Then strip
approximately 0.25 inch (0.6 cm) of
insulation off of each Control cable wire.
5. Strip approximately 0.25 inch (0.6 cm) of insulation off of each power, alarm and auxiliary wire.
6. Install a BNC male connector to the video (coaxial) cable.
7. Make all wiring connections to the terminal blocks as shown in Figure 21 and with reference to Table 4
and Table 8. In simplex configuration, the COMMAND IN + (CI+) and COMMAND IN - (CI-) terminals
must be connected. If the Surveyor is daisy-chained, the COMMAND OUT + (CO+) and COMMAND OUT
- (CO-) terminals must also be used. The response lines RO+, RO-, RIN+, and RIN- are used for Half-
Duplex configuration only.
WARNING
: If Vicoax mode is being used, DO NOT wire TB1 for RS-422 mode, as this will cause the Mini
Dome program to lock up upon power-up.
8. Pull the cables back through the top of the Housing until approximately 12 inches (30.5 cm) of each cable
remains in the Housing.
9. Reinstall the terminal blocks TB1, TB2, TB3 and TB4 into to the Customer Interface Board at the proper
block frames.
WARNING
: Failure to install the terminal blocks into the correct frames can cause damage to the CPU and
other electrical components in the Housing upon power-up.
10. Install the video BNC cable connector to the Customer Interface Board’s mating BNC connector.
11. Remove the screws from the Strain Relief Clamps and conveniently insert all wires. Screw the clamps
loosely back onto the board and pivot each Strain Relief Ring for optimum positioning. Conveniently
route the wires to their individual connections, leaving an approximate 3 inch (7.5 cm) loop in each wire.
Tighten the Strain Relief clamp screws. Pull the remainder of the cable back through the top of the
Housing until the wiring comfortably passes directly from the Cable Clamp to the top of the Housing.
X971 Rev 1098 Surveyor Mini Dome System
Wiring
•
17
Содержание surveyor X971
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 10: ...iv X971 Rev 1098 Surveyor Mini Dome System ...
Страница 20: ...NOTES 6 Drive Mechanism Assembly X971 Rev 1098 Surveyor Mini Dome System ...
Страница 36: ...NOTES 22 Final Assembly X971 Rev 1098 Surveyor Mini Dome System ...
Страница 42: ...NOTES 28 Operation X971 Rev 1098 Surveyor Mini Dome System ...
Страница 44: ...NOTES 30 Maintenance X971 Rev 1098 Surveyor Mini Dome System ...
Страница 46: ...NOTES 32 Shipping Instructions X971 Rev 1098 Surveyor Mini Dome System ...
Страница 53: ...X971 Rev 1098 Surveyor Mini Dome System Technical Information 39 NOTES ...