AA-800 / AA-800T rev.03
ZONE # 1
75.0
o
F
SELECT ZONE
(1 .. 8): _
4.5 ZONE STATUS DISPLAY
Definition:
You can display zone status information at any time by using the
Zone
key. This key also allows you to modify certain zone parameters such as set points
without having to reconfigure the zone. The current zone definition and data readings
are displayed along with the zone status. The information displayed depends on the
type of zone:
1. Dry contact zones:
OPEN / CLOSE, recognition time
2. Temperature zones: temperature reading, set points, critical temperature
and recognition time.
3. Pulse count zones:
pulse count, set points and observation length
When using the outdoor temperature compensation feature, the zone assigned to the
outdoor probe is identified by the message OUTDOOR PROBE (See Section 4.3). The
different zone states are summarized below:
1.
DISABLED
: When a zone is first configured, it is in disabled state, until the
user activates it using the Activate key. When a zone is disabled, no alarms
are detected on the zone input. The zone LED on the front panel is turned off.
2.
ACTIVATED
: Alarm detection is enabled on the zone input. The zone LED
on the front panel is turned on. To change the state to BYPASSED, use the
Bypass/Activate key.
3.
BYPASSED
: No alarm detection is performed on the zone input. The LED on
the front panel blinks slowly. To change the state to ACTIVATED, use the
Bypass/Activate key.
4.5.1 Viewing and Modifying Dry Contact Zones
The recognition time of a dry contact zone can be modified using the Zone key as
follows. Refer to section 3.2 of the installation manual for further information about
dry contact zones and recognition time.
1. Press the
Zone
key
Zone
.
2. Enter the number of the zone. The state of the zone is displayed, followed by the
status.