AA-800 / AA-800T rev.03
2.6 16 VAC POWER FAILURE ALARM
Definition:
This parameter defines the time the system waits before setting off an
alarm in the case of a power failure on the system 16.5VAC input (wall mount trans-
former). It can be enabled or disabled and the delay ranges from 0 seconds to 59
minutes 59 seconds. The default setting is ENABLED with a value of 30 minutes.
Setting:
1. Press the
Power Failure
JKL
key. The system displays the current status of the
Power Failure feature along with the current delay.
2. Type
Enter
to modify the current settings or
Cancel
to exit this function.
3. Type
1
to modify the status.
To Activate / Deactivate Alarm:
ENABLE . . . . . . . (1)
DISABLE. . . . . . . (2)
4. Type
1
to activate, or
2
to deactivate the alarm. The new status is displayed and
the system returns to the Date/Time display.
STATUS . . . . . . . (1)
DELAY . . . . . . . . (2)
STATUS . . . . . . . (1)
DELAY . . . . . . . . (2)
3. Type
2
to adjust the delay.
To Adjust the Delay:
RANGE FROM
(0 .. 59 MIN, 0 .. 59 SEC)
TO MODIFY. . . . . (
↵
↵↵
↵↵
)
TO QUIT. . . . . . . (X)