98MANALIDP10AV Rev. A 8/16/11
Table 6. Error Messages (Continued)
Message
Interpretation
BADZERO
Recalculation of offset during
CAL AT0
,
CAL LRV
, or
EX ZERO
resulted in out
of range value.
a. Applied pressure too high during operation.
b. Improper calibration setup.
BADSPAN
Recalculation of slope during
CAL URV
operation resulted in out of range value.
a. Applied pressure too low during
CAL URV
operation.
b. Improper calibration setup.
BAD LRV
Entered value for
EGU LRV
is outside sensor limits.
BAD URV
Entered value for
EGU URV
is outside sensor limits.
BAD RNG
Recalculation of turndown during
EGU LRV
or
EGU URV
resulted in out
of range value. Entered values for
EGU LRV
and/or
EGU URV
were either
too close together or too far apart
.
RNG>EGU
Recalculation of display value for
EGU LRV
or
EGU URV
resulted in out of range
value. Selection of (linear)
EGU
units caused display to overflow.
LRVNOT0
Attempting mode change from
LINEAR
to
SQ<1CUT
or
SQ<4LIN
when
EGU LRV
is not 0.0.