[10]
98MANALIDP10AV Rev. A 8/16/11
Electrical Ground Connections
The transmitter is equipped with an internal ground connection within the field wiring
compartment and an external ground connection at the base of the electronics housing.
To minimize galvanic corrosion, place the wire lead or terminal between the captive
washer and loose washer on the external ground screw. If shielded cable is used, earth
(ground) the shield at the field enclosure only. Do not ground the shield at the
transmitter.
Test Points
The banana plug receptacles (designated CAL) can be used to check transmitter output of
the IDP10-A. Measurements should be 100 to 500 mV dc for 0 to 100% transmitter
output. Refer to Figure 9.
HHT Terminals
As the top terminal is blocked, this transmitter does not communicate with the HHT, PC10,
PC20, HART Communicator, or IFDC.
Approximate Mass
Without Process Connectors
3.5 kg (7.8 lb)
With Process Connectors
4.2 kg (9.2 lb)
With Optional 316 ss Housing Add 1.1 kg (2.4 lb)
Process Wetted Materials
Diaphragm: 316L ss, Co-Ni-Cr, Hastelloy C, gold plated 316L ss, Monel, or tantalum
Covers and Process Connections: 316 ss, carbon steel, Hastelloy C, Monel, or pvdf inserts
Product Safety Specifications
!
DANGER
To prevent possible explosions and to maintain explosion proof, dust-ignition proof
protection, observe applicable wiring practices. Plug unused conduit opening with the
provided metal pipe plug, which engages a minimum of five full threads.
!
WARNING
To maintain IEC IP66 and NEMA Type 4X protection, the unused conduit opening
must be plugged. In addition, the threaded housing covers must be installed.
Turn covers until O-ring contacts housing; then continue to hand tighten as much
as possible (at least 1/4 turn).
Содержание IDP10-A
Страница 14: ... 14 98MANALIDP10AV Rev A 8 16 11 ...
Страница 16: ... 16 98MANALIDP10AV Rev A 8 16 11 ...
Страница 26: ... 26 98MANALIDP10AV Rev A 8 16 11 ...
Страница 35: ... 35 98MANALIDP10AV Rev A 8 16 11 ...
Страница 37: ... 37 98MANALIDP10AV Rev A 8 16 11 IDP10 A and IDP10 V Calibration ...
Страница 40: ... 40 98MANALIDP10AV Rev A 8 16 11 IDP10 A and IDP10 V Configuration ...