Viatran DL Series 

Analog Input Process Meter 

Instruction Manual 

Содержание DL-ACB0N

Страница 1: ... Drive Tonawanda New York USA 14150 Phone 1 716 629 3800 Fax 1 716 693 9162 Toll Free 1 800 688 0030 Email solutions viatran com Website www viatran com Viatran DL Series Analog Input Process Meter Instruction Manual ...

Страница 2: ...ications or applications where malfunctioning could result in personal injury or property loss Anyone using this product for such applications does so at his her own risk Viatran Corporation shall not be held liable for damages resulting from such improper use Limited Warranty Viatran warrants this product against defects in material or workmanship for the specified period under Specifications fro...

Страница 3: ...ting Dimensions 16 Configuration for 12 or 24 VDC Power Option 17 Transmitter Supply Voltage Selection P P 18 Connections 18 Connectors Labeling 19 Power Connections 19 Signal Connections 20 Modbus RTU Serial Communications 21 Relay Connections 21 Switching Inductive Loads 22 F4 Digital Input Connections 23 4 20 mA Output Connections 23 Analog Output Transmitter Power Supply 23 External Relays Dig...

Страница 4: ...ail Safe Operation 46 Programming Time Delay 46 Relay Action for Loss of 4 20 mA Input Loop Break 46 Relay and Alarm Operation Diagrams 47 High Alarm Operation Set Reset 47 Low Alarm Operation Set Reset 48 High Alarm with Fail Safe Operation Set Reset 49 Low Alarm with Fail Safe Operation Set Reset 50 Pump Alternation Control Operation 51 Relay Sampling Operation 52 Signal Loss or Loop Break Relay...

Страница 5: ...ng AoutPr 76 Programmable Function Keys User Menu user 77 Tare tare 78 Internal Source Calibration ICAL 78 METER OPERATION 81 Front Panel Buttons Operation 81 Function Keys Operation 81 F4 Operation 82 Maximum Minimum Readings 82 TROUBLESHOOTING 83 Diagnostics Menu diag 83 Determining Software Version 83 Reset Meter to Factory Defaults 84 Factory Defaults User Settings 85 Troubleshooting Tips 88 T...

Страница 6: ...UCTION The DL series analog input process meter is a multi purpose easy to use digital process meter ideal for level flow rate temperature or pressure transmitter applications It accepts current and voltage signals e g 4 20 mA 0 10 V Three of the front panel buttons can be custom programmed for a specific operation The analog input can be scaled to display the process in two different scales for e...

Страница 7: ...lays 4 20 mA output DL ACB4R DL DCB4R 4 relays 4 20 mA output Accessories Model Description 350PDA1002 DIN rail mounting kit for two expansion modules 350PDA1004 4 SPST Form A relays 350PDA1044 4 digital inputs 4 digital outputs 2 may be connected 350PDA1232 RS 232 serial adapter 350PDA1485 RS 485 serial adapter 350PDA7485 I RS 232 to RS 422 485 isolated converter 350PDA7485 N RS 232 to RS 422 485...

Страница 8: ...ON All ranges are calibrated at the factory Recalibration is recommended at least every 12 months MAX MIN DISPLAY Max min readings reached by the process are stored until reset by the user or until power to the meter is turned off PASSWORD Three programmable passwords restrict modification of programmed settings Pass 1 Allows use of function keys and digital inputs Pass 2 Allows use of function ke...

Страница 9: ...range 40 to 65 C Storage temperature range 40 to 85 C Relative humidity 0 to 90 non condensing CONNECTIONS Removable screw terminal blocks accept 12 to 22 AWG wire RJ45 for external relays digital I O and serial communication adapters ENCLOSURE 1 8 DIN high impact plastic UL 94V 0 color black MOUNTING 1 8 DIN panel cutout required 3 622 x 1 772 92 mm x 45 mm Two panel mounting bracket assemblies a...

Страница 10: ... 1 0001 to 2 9999 ROUND H TANK Diameter Length 999 999 inch or cm calculates volume in gallons or liters respectively LOW FLOW CUTOFF 0 999999 0 disables cutoff function DECIMAL POINT Up to five decimal places or none d ddddd d dddd d ddd d dd d d or dddddd CALIBRATION RANGE Input Range Minimum Span Input 1 Input 2 4 20 mA 0 15 mA 10 V 0 01 V An error message will appear if the input 1 and input 2...

Страница 11: ...ing based on time Off disable unused relays and enable Interlock feature Manual on off control mode TIME DELAY 0 to 999 9 seconds on off relay time delays Programmable and independent for each relay AUTO INITIALIZATION When power is applied to the meter relays will reflect the state of the input to the meter RELAY RESET User selectable via front panel buttons or digital inputs 1 Automatic reset on...

Страница 12: ...rift is separate from input drift ISOLATED TRANSMITTER POWER SUPPLY Terminals I R 24 VDC 10 May be used to power the 4 20 mA output or other devices Refer to Figure 5 on page 17 and Figure 16 on page 23 All models rated 40 mA max EXTERNAL LOOP POWER SUPPLY 35 VDC maximum OUTPUT LOOP RESISTANCE Power supply Minimum Maximum 24 VDC 10 Ω 700 Ω 35 VDC external 100 Ω 1200 Ω Modbus RTU Serial Communicati...

Страница 13: ...issions Class A AC Mains Conducted Emissions Class A IMMUNITY EN 61326 1 2013 Measurement control and laboratory equipment EN 61000 6 2 2005 EMC heavy industrial generic immunity standard RFI Amplitude Modulated 80 1000 MHz 10 V m 80 AM 1 kHz 1 4 2 0 GHz 3 V m 80 AM 1 kHz 2 0 2 7 GHz 1 V m 80 AM 1 kHz Electrical Fast Transients 2kV AC mains 1kV other Electrostatic Discharge 4kV contact 8kV air RFI...

Страница 14: ...ury Warning Hazardous voltages exist within enclosure Installation and service should be performed only by trained service personnel INSTALLATION There is no need to remove the meter from its case to complete the installation wiring and setup of the meter for most applications Instructions are provided for setting up a 12 24 VDC powered meter to operate from 12 VDC and for changing the transmitter...

Страница 15: ... is 6 4 mm or less through the bracket Slide the bracket toward the front of the case and remove Insert meter into the panel cutout Install mounting brackets and tighten the screws against the panel To achieve a proper seal tighten the mounting bracket screws evenly until meter is snug to the panel along its short side DO NOT OVER TIGHTEN as the rear of the panel may be damaged Figure 1 1 8 DIN Pa...

Страница 16: ...Viatran DL Series Analog Input Process Meter Instruction Manual 16 Mounting Dimensions Figure 3 Meter Dimensions Side View Figure 4 Meter Dimensions Top View NO NC NC C NO C NO NC NC C NO C R ...

Страница 17: ...er option are shipped from the factory ready to operate from 24 VDC To configure the meter for 12 VDC power 1 Remove all the connectors 2 Unscrew the back cover 3 Slide the back cover about 1 inch 4 Configure the J9 jumper located behind the power connector for 12 V as shown below Figure 5 Jumper Configuration for 12 24 VDC Power MAIN BOARD 24 VDC 12 VDC POWER J9 12 V 24 V J9 CONFIGURATION Factory...

Страница 18: ...the wiring connectors 2 Unscrew the back cover 3 Slide out the back cover by about 1 inch 4 Configure the J4 jumper located behind the input signal connector for the desired excitation voltage as shown Figure 6 Transmitter Supply Voltage Selection Connections All connections are made to removable screw terminal connectors located at the rear of the meter Use copper wire with 60 C or 60 75 C insula...

Страница 19: ...les cables or meters to the RJ45 M LINK connector Otherwise damage will occur to the equipment and the meter Figure 7 Connector Labeling for Fully Loaded Meter Power Connections Power connections are made to a two terminal connector labeled POWER on Figure 7 on page 19 The meter will operate regardless of DC polarity connection The and symbols are only a suggested wiring convention Figure 8 Power ...

Страница 20: ...e are no switches or jumpers to set up for current and voltage inputs Setup and programming is performed through the front panel buttons Figure 9 Transmitters Powered by Internal Supply Figure 10 Transmitter Powered by Ext Supply or Self Powered The current input is protected against current overload by a resettable fuse The display may or may not show a fault condition depending on the nature of ...

Страница 21: ...485 or the 350PDA8008 for USB The same port is used for interfacing with all expansion modules e g external relays digital I O Relay Connections Relay connections are made to two six terminal connectors labeled RELAY1 RELAY4 on Figure 7 Each relay s C terminal is common only to the normally open NO and normally closed NC contacts of the corresponding relay The relays C terminals should not be conf...

Страница 22: ...t across the contacts C 0 5 to 1 µF for each amp through closed contacts Notes 1 Use capacitors rated for 250 VAC 2 RC networks may affect load release time of solenoid loads Check to confirm proper operation 3 Install the RC network at the meter s relay screw terminals An RC network may also be installed across the load Experiment for best results Figure 14 Low Voltage DC Loads Protection RC Netw...

Страница 23: ...er output are made to the connector terminals labeled MA OUT The 4 20 mA output may be powered internally or from an external power supply Figure 16 4 20 mA Output Connections Analog Output Transmitter Power Supply The internal 24 VDC power supply powering the analog output may be used to power other devices if the analog output is not used The I terminal is the 24 V and the R terminal is the retu...

Страница 24: ... they are used to connect additional modules to the system Note The jumper located between the RJ45 connectors of the 350PDA1044 must be removed on the second digital I O module in order for the system to recognize it as module 2 Warning Do not connect or disconnect the expansion modules with the power on More detailed instructions are provided with each optional expansion module Figure 17 Expansi...

Страница 25: ...his feature is enabled by configuring the relay and relative digital input s see page 62 In one example dry interlock contacts are connected in series to one digital input which will be used to force on energize the assigned interlock power relay when all interlock contacts are closed safe The interlock relay front panel LED flashes when locked out The interlock relay would be wired in series with...

Страница 26: ...ead in milliamps and volts depending on the input selection The calibration equipment is certified to NIST standards Overview There are no jumpers to set for the meter input selection Setup and programming is done through the front panel buttons After power and input signal connections have been completed and verified apply power to the meter ...

Страница 27: ... digit Press the Enter button to access a menu or to accept a setting Press and hold the Menu button for three seconds to access the advanced features of the meter Button Symbol Description LED Status Menu 1 8 Alarm 1 8 indicator Right arrow F1 1 8 M Flashing Relay in manual control mode Up arrow F2 T Flashing Tare Enter F3 1 8 Flashing Relay interlock switch open Note F4 is a digital input Alarms...

Страница 28: ...pt Decimal point Set decimal point Pv 1 PV1 PV1 decimal point Level Pv 2 PV2 PV2 decimal point Level prog Program Enter the Program menu SCALE Scale Enter the Scale menu SCAL 1 Scale 1 Enter the Scale menu for PV1 SCAL 2 Scale 2 Enter the Scale menu for PV2 Cal Calibrate Enter the Calibration menu Inp 1 Input 1 Calibrate input 1 signal or program input 1 value Dis 1 Display 1 Program display 1 val...

Страница 29: ... control Sanmpl Sampling Set relay for sampling operation OFF Off Disable relay and front panel status LED Select Off to enable Interlock feature Set 1 Set 1 Program set point 1 RSt 1 Reset 1 Program reset point 1 RLY 2 Relay 2 Relays 2 8 setup Note Relays 5 8 are shown only if expansion relay module is installed FaiLSF Fail safe Enter Fail safe menu FLS 1 Fail safe 1 Set relay 1 fail safe operati...

Страница 30: ...ut 2 value e g 20 000 mA reset Reset Press Enter to access the Reset menu Rst Hi Reset high Press Enter to reset max display Rst Lo Reset low Press Enter to reset min display Rst HL Reset high low Press Enter to reset max min displays Rst tr Reset tare Reset tare Contrl Control Enter Control menu Auto Automatic Press Enter to set meter for automatic operation mAn Manual Press Enter to manually con...

Страница 31: ...ress Menu button to enter Programming Mode then press the Up arrow button to scroll main menu Press Menu at any time to exit and return to Run Mode Changes made to settings prior to pressing Enter are not saved Changes to the settings are saved to memory only after pressing Enter F3 The display moves to the next menu every time a setting is accepted by pressing Enter F3 ...

Страница 32: ... next digit and Up arrow to increment digit value The digit being changed is displayed brighter than the rest Press and hold up arrow to auto increment the display value Press the Enter button at any time to accept a setting or Menu button to exit without saving changes 004 000 004 000 005 000 dis 1 dis 1 dis 1 Next Setting Select Next Digit Increment Digital Value Accept Setting ...

Страница 33: ...lay operation 8 4 20 mA analog output scaling Press the Enter button to access any menu or press Up arrow button to scroll through choices Press the Menu button to exit at any time Note Scal 1 Scal 2 are displayed instead of Scale if d SCAL is selected under the Setup Input menu They correspond to the PV1 PV2 scales Enter custom units here Note Use the d SCAL selection to activate the dual scale l...

Страница 34: ...mA or 4 20 mA signals The voltage input is capable of accepting any signal from 10 to 10 VDC Select voltage input to accept 0 5 1 5 0 10 or 10 VDC signals After selecting mA or Volt input d SCAL is displayed press Enter to select Yes or No Selecting Yes enables the dual scale feature which allows for the Scale SCALE and Units units menus to be used to scale the same input in two different scales f...

Страница 35: ...nits or custom legends can be set using the following 7 segment character set Display Character Display Character 0 0 k K 1 1 l L 2 2 m m 3 3 n n 4 4 O O 5 5 o o 6 6 p P 7 7 q q 8 8 r r 9 9 s S A A t t b b u u C C v V c c u w w d d x X e E y Y f F z Z g G 9 g H H h h I I I i Degree j J Space Notes Degree symbol represented by if programming with MeterView Pro The letters m and w use two 7 segment ...

Страница 36: ...places or with no decimal point at all Pressing the Right arrow moves the decimal point one place to the right until no decimal point is displayed and then it moves to the leftmost position Pressing the Up arrow moves the decimal point one place to the left If the dual scale level feature is selected the decimal point selections for PV1 PV2 are enabled ...

Страница 37: ...enus Note The Scale and Calibrate functions are exclusive of each other The meter uses the last function programmed Only one of these methods can be employed at a time The Scale and Calibrate functions can use up to 32 points default is 2 The number of points should be set in the Advanced menu under the Multi Point Linearization Linear menu selection prior to scaling and calibration of the meter s...

Страница 38: ...ailable for free download at www predig com Data logging for one meter at a time is available with MeterView Pro software More advanced data acquisition may be accomplished by using any Modbus RTU compliant software In order to program the meter using a computer the meter must be connected using a USB RS 232 or RS 485 serial adapter see ORDERING INFORMATION on page 7 for details Scaling the Meter ...

Страница 39: ...alog input can be displayed in two different scales by enabling the dual scale feature d SCAL in the Setup Input menu see page 33 To enable the dual scale feature for some level applications you must select d SCAL in the Input selection menu Scaling the Input for PV1 SCAL 1 Scaling the Input for PV2 SCAL 2 ...

Страница 40: ... signal to be applied or programmed The error message might be caused by any of the following conditions 1 Input signal is not connected to the proper terminals or it is connected backwards 2 Wrong signal selection in Setup menu 3 Minimum input span requirements not maintained 4 Input 1 signal inadvertently applied to calibrate input 2 Minimum Input Span The minimum input span is the minimum diffe...

Страница 41: ...ge 38 The meter can be calibrated to display the process variable in engineering units by applying the appropriate input signal and following the calibration procedure The use of a calibrated signal source is strongly recommended to calibrate the meter Warm up the meter for at least 15 minutes before performing calibration to ensure specified accuracy The display flashes while sensing the inputs ...

Страница 42: ...ss 9 Toggle net gross The small display Little can be programmed to display 1 Unit 2 Process value 1 PV1 3 Process value 2 PV2 4 Percent of PV1 PCT 5 Relay set points 6 Max min values 7 Engineering units or custom legends 8 Modbus input 9 Off no display 10 Toggle reading and units 11 Display gross 12 Toggle net gross Display Intensity The meter has eight display intensity levels to give the best p...

Страница 43: ...l 43 Display Setup Menu After setting up the input and display press the Menu button to exit programming and skip the rest of the setup menu Press the Menu button again and the Up arrow to reach the Program menu and complete the scaling or calibration of the meter ...

Страница 44: ...y after alarm condition has cleared e Pump alternation control automatic reset only f Sampling the relay is activated for a user specified time g Off relay state controlled by Interlock feature 2 Set point 3 Reset point 4 Fail safe operation a On enabled b Off disabled 5 Time delay a On delay 0 999 9 seconds b Off delay 0 999 9 seconds 6 Relay action for loss break of 4 20 mA input ignore on off C...

Страница 45: ...reset non latching 2 Automatic manual reset at any time non latching 3 Latching manual reset only at any time 4 Latching with Clear manual reset only after alarm condition has cleared 5 Pump alternation control automatic reset only 6 Sampling the relay is activated for a user specified time 7 Off relay state controlled by Interlock feature The following graphic shows relay 1 action setup relay 2 8...

Страница 46: ...l safe operation is set independently for each relay Select on to enable or select off to disable fail safe operation Programming Time Delay The On and Off time delays may be programmed for each relay between 0 and 999 9 seconds The relays will transfer only after the condition has been maintained for the corresponding time delay The On time delay is associated with the set point The Off time dela...

Страница 47: ...tion Diagrams The following graphs illustrate the operation of the relays status LEDs and ACK button High Alarm Operation Set Reset For Manual reset mode ACK can be pressed anytime to turn off relay To detect a new alarm condition the signal must go below the set point and then go above it ...

Страница 48: ...to turn off relay For relay to turn back on signal must go above set point and then go below it Reset Set Input Relay LED energized de energized on off Relay LED Automatic or Manual non latching ACK pressed Relay LED Manual latching ACK pressed Relay LED ACK pressed Automatic non latching Manual only after passing above Reset latching with clear ...

Страница 49: ... energized in non alarm condition In case of power failure relay will go to alarm state Relay Input Automatic non latching energized de energized off on Relay LED Automatic or Manual non latching ACK pressed Relay LED Manual latching ACK pressed Relay LED Manual only after passing below Reset latching with clear ACK pressed Set LED ...

Страница 50: ...rgized in non alarm condition In case of power failure relay will go to alarm state Reset Set Input Relay LED Automatic non latching de energized energized on off Relay LED Automatic or Manual non latching ACK pressed Relay LED Manual latching ACK pressed Relay LED Manual only after passing above Reset latching with clear ACK pressed ...

Страница 51: ...Viatran DL Series Analog Input Process Meter Instruction Manual 51 Pump Alternation Control Operation ...

Страница 52: ... the relay trips and the sample time starts After the sample time has elapsed the relay resets The cycle repeats every time the set point is crossed going up for high alarms and going down for low alarms The sample time can be programmed between 0 1 and 5999 9 seconds Set Reset Relay LED Input Sample Time Sample Time Sample Time ...

Страница 53: ...or a high alarm relay When the meter detects a break in the 4 20 mA loop the relay will go to one of the following selected actions 1 Turn On Go to alarm condition 2 Turn Off Go to non alarm condition 3 Ignore Processed as a low signal condition Relay LED Input Loop Break Ignore de energized energized off on Relay LED Loop Break Off Relay LED Loop Break On Set Reset ...

Страница 54: ...y timer starts and the relay trips when the time delay has elapsed If the signal drops below the set point high alarm before the time delay has elapsed the On time delay timer resets and the relay does not change state The same principle applies to the Off time delay Note If Automatic or Manual A mAn reset mode is selected the LED follows the reset point and not the relay state when the relay is a...

Страница 55: ...dband 3 Sampling Based on Time 4 Pump Alternation Control for up to 8 Pumps Relays Auto Initialization When power is applied to the meter the front panel LEDs and alarm relays will reflect the state of the input to the meter The following table indicates how the alarm LEDs and relays will react on power up based on the set and reset points Alarm HI or LO Alarm Set Point Reset Point Power Up Readin...

Страница 56: ...ferently for latching and non latching relays For non latching relays the LED is always off during normal condition and always on during alarm condition regardless of the state of the relay e g Relay acknowledged after alarm condition For latching relays the alarm LEDs reflect the status of the relays regardless of the alarm condition The following tables illustrate how the alarm LEDs function in ...

Страница 57: ... Alarm On On Normal Off Off Next Alarm On On Ack On Off Normal Off Off In this application the meter is set up for automatic and manual reset at any time non latching relay The LED and the relay automatically reset when the meter returns to the normal condition The next time an alarm occurs the operator acknowledges the alarm manually while the alarm condition still exists This causes the relay to...

Страница 58: ...mal condition This is because for latching relays the alarm LED reflects the status of the relay regardless of the alarm condition Acknowledging Relays There are two ways to acknowledge relays programmed for manual reset 1 Via the programmable front panel function keys F1 F3 Default F3 assigned to ACK 2 Remotely via a normally open pushbutton wired across one of the digital inputs and the 5 V term...

Страница 59: ... 2 3 4 000 9 000 Controls low alarm 4 40 000 29 000 Controls high alarm Pump Alternation Operation 1 Pump 1 turns on when level reaches 30 000 when level drops below 10 000 pump 1 turns off 2 The next time level reaches 30 000 pump 2 turns on when level drops below 10 000 pump 2 turns off 3 If the level doesn t reach 35 000 pump 1 and pump 2 will be operating alternately 4 If pump 1 cannot keep th...

Страница 60: ...nt Function 1 495 750 Controls low alarm 2 7500 6900 Controls high alarm 3 7000 900 Controls backup pump 4 6000 1000 Controls main pump The following graphics provide a visual representation of a typical pump alternation application with high and low alarm monitoring 1 Relay 4 turns the main pump on at 6000 gallons and turns it off at 1000 gallons 2 With the Pump Alternation feature activated the ...

Страница 61: ...backup pump is not able to keep up and the level reaches 7000 gallons relay 4 transfers and starts the main pump as well 4 Relay 2 trips the High Level Alarm at 7500 gallons and resets at 6900 gallons 5 Relay 1 trips the Low Level Alarm at 495 gallons and resets at 750 gallons ...

Страница 62: ...interlock feature 1 Access the Setup Relay Action menu and set the action to off 2 In the Advanced features User menu program any of the digital inputs to Force On any of the internal relays 1 4 3 Connect a switch or dry contact between the 5V terminal and the corresponding digital input dI 1 to dI 4 terminal 1 2 3 4 5 6 5 I1 I2 I3 I4 O1 7 8 O2 O3 9 10 O4 G DI 1 4 DO 1 4 5 VDC GND SW2 SW1 ...

Страница 63: ...k relay is re activated by the digital inputs switches Note If multiple digital inputs are assigned to the same relay then the corresponding logic is AND i e both switches must be closed to trip the relay Scaling the 4 20 mA Analog Output Aout The 4 20 mA analog output can be scaled to provide a 4 20 mA signal for any display range selected No equipment is needed to scale the analog output simply ...

Страница 64: ... time by selecting reset high low rst HL The tare value used to zero the display may be reset by selecting reset tare rst tr Control Menu Contrl The Control menu is used to control the 4 20 mA analog output and the relays manually ignoring the input Each relay and analog output can be programmed independently for manual control Selecting automatic control sets all relays and analog output for auto...

Страница 65: ... of function keys digital inputs and editing set reset points Pass 3 Restricts all programming function keys and digital inputs Protecting or Locking the Meter Enter the Password menu and program a six digit password For instructions on how to program numeric values see Setting Numeric Values page 32 Record the password for future reference If appropriate it may be recorded in the space provided M...

Страница 66: ...d protection access the Password menu and enter the correct password twice as shown below The meter is now unprotected until a new password is entered If the correct six digit password is entered the meter displays the message unLoc unlocked and the protection is disabled until a new password is programmed If the password entered is incorrect the meter displays the message Locd Locked for about tw...

Страница 67: ...truction Manual 67 Advanced Features Menu To simplify the setup process functions not needed for most applications are located in the Advanced Features menu Press and hold the Menu button for three seconds to access the advanced features of the meter ...

Страница 68: ...unction cutoff out Functn Signal input conditioning Select linear square root programmable exponent or round horizontal tank function Linear Linear Set meter for linear function and select number of linearization points Pv 1 PV1 Select PV1 number of linearization points Pv 2 PV2 Select PV2 number of linearization points No PtS Number of points Set PV1 for 2 to 32 point linearization Set PV2 for 2 ...

Страница 69: ...ys and digital I O F1 F1 function key Assign F1 function key F2 F2 function key Assign F2 function key F3 F3 function key Assign F3 function key F4 F4 function Assign F4 function digital input dI I Digital input 1 Assign digital input 1 8 if expansion modules are connected dO 1 Digital output 1 Assign digital output 1 8 if expansion modules are connected ICal Internal source calibration Enter inte...

Страница 70: ...pass value Round Round Round value Functn Function Function selected SCALE Scale Scaling parameter Cutoff Cutoff Cutoff value Dsplay Display Display assignments RELAY Relays Relay settings Aout Analog output Analog output scaling Aoutpr Analog output programming Analog output programming SEriaL Serial Serial communication settings LED t LED test Test all LEDs Info Information Display software and ...

Страница 71: ... behavior of the meter so that small variations in the signal are filtered out but large abrupt changes in the input signal are displayed immediately The bypass value determines the minimum amount of signal change to be displayed immediately All signal changes smaller than the bypass value are filtered or averaged by the meter The noise filter bypass may be set between 0 1 and 99 9 of full scale R...

Страница 72: ...led instructions are provided with each optional serial communications adapter Note Refer to the Modbus Register Tables located at www viatran com for details When using more than one meter in a multi drop mode each meter must be provided with its own unique address The meter address Slave ID may be programmed between 1 and 247 The transmit delay may be set between 0 and 199 ms The parity can be s...

Страница 73: ...t linearization is part of the linear function selection Signal Input Conditioning Functn The Function menu is used to select the signal input conditioner applied to the input linear square root programmable exponent or round horizontal tank volume calculation The multi point linearization is part of the linear function selection Meters are set up at the factory for linear function with 2 point li...

Страница 74: ...ions using weirs and flumes Multi Point Linearization Linear Meters are set up at the factory for linear function with 2 point linearization Up to 32 linearization points can be selected for PV1 under the linear function The multi point linearization can be used to linearize the display for non linear signals such as those from level transmitters used to measure volume in odd shaped tanks or to co...

Страница 75: ...le is displayed continue pressing the Enter button until the meter completes the scaling of the input and display values Changing the Volume from Gallons to Liters In the above graphic entering the 48 for the diameter and 120 for the length of the round horizontal tank the meter automatically calculates that the volume of the tank is 940 02 gallons 1 Convert gallons to liters 1 US gallon 3 7854 L ...

Страница 76: ... 2 Overrange Analog output value with display in overrange condition 3 Underrange Analog output value with display in underrange condition 4 Break Analog output value when loop break is detected 5 Max Maximum analog output value allowed regardless of input 6 Min Minimum analog output value allowed regardless of input 7 Calibrate Calibrate the internal 4 20 mA source reference used to scale the 4 2...

Страница 77: ...I O Available Settings Display Description Display Description Rst HL Reset max min Contrl Control Menu tare Capture tare disabl Disable function key Rst tr Reset tare AcH Acknowledge relays relay Relay menu reset Reset Menu Set 1 Set point 1 8 Rst Hi Reset max Rly d Disable all relays Rst Lo Reset min Rly E Enable all relays menu Menu button O Hold Relays output hold Right Right arrow button F1 d...

Страница 78: ...ad in milliamps and volts depending on the input selection The calibration equipment is certified to NIST standards The use of calibrated signal sources is necessary to calibrate the internal source of the meter The meter s internal source is what allows the user to scale the meter without applying a signal Check calibration of the meter at least every 12 months Each input must be recalibrated sep...

Страница 79: ... digit is the active digit that can be changed by pressing the Up arrow button Press the Right arrow button to move to the next digit 6 Set the display value to correspond to the input signal being calibrated typically 4 000 mA 7 The display moves to the high input calibration C Hi Apply the high input signal and press Enter 8 Set the display for the high input calibration in the same way as it wa...

Страница 80: ...following conditions 1 Input signal is not connected to the proper terminals or it is connected backwards 2 Wrong signal selection in Setup menu 3 Minimum input span requirements not maintained Minimum Input Span The minimum input span is the minimum difference between input 1 and input 2 signals required to complete the calibration or scaling of the meter Input Range Input 1 Input 2 Span 4 20 mA ...

Страница 81: ...te level in feet and the second display could indicate the volume in gallons Additionally the meter can be set up to display the analog input on the main display and the Modbus input on the second display The relays and analog output can be programmed to operate from the Modbus PV input Front Panel Buttons Operation Button Symbol Description Press to enter or exit Programming Mode view settings or...

Страница 82: ...ser menu 2 Display continuously by assigning either display to max min through the Display menu Any of the F1 F3 function keys buttons and the digital inputs can be programmed to reset the max min readings The meters are set at the factory to display the max reading by pressing the Up arrow F2 button and to use the Right arrow F1 button to access the Reset menu To display max reading using functio...

Страница 83: ...access Diagnostics menu see Advanced Features Menu page 67 It provides an easy way to view the programmed parameter settings for troubleshooting purposes Press the Enter button to view the settings and the Menu button to exit at any time For a description of the diagnostic messages see Advanced Features Menu Display Messages page 68 Determining Software Version To determine the software version of...

Страница 84: ...enu See Advanced Features Menu page 67 2 Press Up arrow to go to Diagnostics menu 3 Press and hold Right arrow for three seconds press Enter when display flashes reset Note If Enter is not pressed within three seconds the display returns to the Diagnostics menu 4 The meter goes through an initialization sequence similar as on power up and loads the factory default settings Note The dual scale sele...

Страница 85: ... scale Filter filter 70 Bypass bypass 0 2 Function Functn Linear Number of points No Pts 2 Programming prog Scale Input 1 InP 1 4 000 mA Display 1 Dis 1 4 000 Input 2 InP 2 20 000 mA Display 2 Dis 2 20 000 Decimal point dd ddd 3 places Cutoff value CutofF 0 000 disabled Display assignment Dsplay Big display Main big PV Process variable Little display Small Little Eng unit default mA Display intens...

Страница 86: ...delay relay 2 On 2 0 0 sec Off delay relay 2 Off 2 0 0 sec On delay relay 3 On 3 0 0 sec Off delay relay 3 Off 3 0 0 sec On delay relay 4 On 4 0 0 sec Off delay relay 4 Off 4 0 0 sec Loop break relay 1 ignore Ignore Loop break relay 2 ignore Ignore Loop break relay 3 ignore Ignore Loop break relay 4 ignore Ignore Display 1 analog out Dis 1 4 000 Output 1 value Out 1 4 000 mA Display 2 analog out D...

Страница 87: ...1 function key F1 Reset max min F2 function key F2 Big display Max Hi F3 function key F3 Acknowledge relays F4 function F4 Acknowledge relays Digital input 1 dI 1 Menu Digital input 2 dI 2 Right arrow Digital input 3 dI 3 Up arrow Digital input 4 dI 4 Enter Digital output 1 dO 1 Alarm 1 Digital output 2 dO 2 Alarm 2 Digital output 3 dO 3 Alarm 3 Digital output 4 dO 4 Alarm 4 Password 1 Pass 1 0000...

Страница 88: ...ling or calibration Display does not respond to input changes reading a fixed number Check 1 Display assignment it might be displaying max min or set point Display alternates between 1 Hi and a number 2 Lo and a number Press Menu to exit max min display readings Relay operation is reversed Check 1 Fail safe in Setup menu 2 Wiring of relay contacts Relay and status LED do not respond to signal Chec...

Страница 89: ...Viatran DL Series Analog Input Process Meter Instruction Manual 89 Figure 22 1 8 DIN Panel Cutout Template ...

Страница 90: ...Viatran DL Series Analog Input Process Meter Instruction Manual 90 This Page Intentionally Left Blank ...

Страница 91: ...Viatran DL Series Analog Input Process Meter Instruction Manual 91 NOTES ...

Страница 92: ...ual 199 Fire Tower Drive Tonawanda New York USA 14150 Phone 1 716 629 3800 Fax 1 716 693 9162 Toll Free 1 800 688 0030 Email solutions viatran com Website www viatran com Support Page www viatran com technical support 98MANALDL_B LIM6000VC_A SFT039 Ver 3 100 up ...