Viatran DL Series Analog Input Process Meter Instruction Manual
69
Display Parameter Action/Setting
Source
Source
Select source for the 4-20 mA output
O-rang
Overrange
Program mA output for display overrange
u-rang
Underrange
Program mA output for display underrange
break
Break
Set input break condition operation
mAx
Maximum
Program maximum mA output allowed
min
Minimum
Program minimum mA output allowed
Calib
Calibrate
Calibrate 4-20 mA output (internal
reference source used for scaling the
output)
4 mA
4 mA output
Enter mA output value read by milliamp
meter with at least 0.001 mA resolution
20 mA
20 mA output
Enter mA output value read by milliamp
meter with at least 0.001 mA resolution
user
User I/O
Assign function keys and digital I/O
F1
F1 function key
Assign F1 function key
F2
F2 function key
Assign F2 function key
F3
F3 function key
Assign F3 function key
F4
F4 function
Assign F4 function (digital input)
dI I
Digital input 1
Assign digital input 1 – 8, if expansion
modules are connected
dO 1
Digital output 1
Assign digital output 1 – 8, if expansion
modules are connected
ICal
Internal source
calibration
Enter internal source calibration (used for
scaling the meter without a signal source)
C CAL
Current
calibration
Calibrate 4-20 mA current input (internal
reference source used for scaling the input)
C lo
Current low
Calibrate low current input (e.g. 4 mA)
C Hi
Current high
Calibrate high current input (e.g. 20 mA)
v CAL
Voltage
calibration
Calibrate voltage input
v Lo
Voltage low
Calibrate low voltage input (e.g. 0 V)
v Hi
Voltage high
Calibrate high voltage input (e.g. 10 V)
Copy
*
Copy*
*For factory use only
Diag
Diagnostics
Display parameter settings
Содержание DL-ACB0N
Страница 51: ...Viatran DL Series Analog Input Process Meter Instruction Manual 51 Pump Alternation Control Operation ...
Страница 89: ...Viatran DL Series Analog Input Process Meter Instruction Manual 89 Figure 22 1 8 DIN Panel Cutout Template ...
Страница 90: ...Viatran DL Series Analog Input Process Meter Instruction Manual 90 This Page Intentionally Left Blank ...
Страница 91: ...Viatran DL Series Analog Input Process Meter Instruction Manual 91 NOTES ...