Viatran DL Series Analog Input Process Meter Instruction Manual
17
Configuration for 12 or 24 VDC Power Option
Warning!
Do not exceed voltage rating of the selected
configuration.
Meters equipped with the 12/24 VDC power option are shipped
from the factory ready to operate from 24 VDC.
To configure the meter for 12 VDC power:
1. Remove all the connectors.
2. Unscrew the back cover.
3. Slide the back cover about 1 inch.
4. Configure the J9 jumper, located behind the power
connector, for 12 V as shown below.
Figure 5. Jumper Configuration for 12/24 VDC Power
MAIN BOARD
24 VDC
12 VDC
POWER
J9
12 V
24 V
J9 CONFIGURATION
Factory
Default
M-LINK
+
_