Viatran DL Series Analog Input Process Meter Instruction Manual
34
Setting the Input Signal (
Input
)
Enter the
Input
menu to set up the meter to display current (
mA
) or
voltage (
volt
) inputs.
The current input is capable of accepting any signal from 0 to 20 mA.
Select current input to accept 0-20 mA or 4-20 mA signals.
The voltage input is capable of accepting any signal from -10 to +10 VDC.
Select voltage input to accept 0-5, 1-5, 0-10, or
±
10 VDC signals.
After selecting
mA
or
Volt
input,
d-SCAL
is displayed; press Enter to
select “
Yes
” or “
No
”. Selecting “
Yes
” enables the dual-scale feature,
which allows for the Scale (
SCALE
) and Units (
units
) menus to be used
to scale the same input in two different scales for PV1 & PV2.
Set
d-SCAL
to no if both displays are to be used for anything
other than PV1 & PV2.