24
Time program TO2 (only in a case, that it is activated)
Parameter
Function
Production settings
Min.
Max.
Units
520
Preselection
Mo-Su
00:00
24:00
hh:mm
521
Mo-Su: 1. Phase on
6:00
00:00
24:00
hh:mm
522
Mo-Su: 1. Phase off
22:00
00:00
24:00
hh:mm
523
Mo-Su: 2. Phase on
24:00
00:00
24:00
hh:mm
524
Mo-Su: 2. Phase off
24:00
00:00
24:00
hh:mm
525
Mo-Su: 3. Phase on
24:00
00:00
24:00
hh:mm
526
Mo-Su: 3. Phase off
24:00
00:00
24:00
hh:mm
536
Standard values
Su
Time program 3/TO3
Parameter
Function
Production settings
Min.
Max.
Units
540
Preselection
Mo-Su
00:00
24:00
hh:mm
541
Mo-Su: 1. Phase on
6:00
00:00
24:00
hh:mm
542
Mo-Su: 1. Phase off
22:00
00:00
24:00
hh:mm
543
Mo-Su: 2. Phase on
24:00
00:00
24:00
hh:mm
544
Mo-Su: 2. Phase off
24:00
00:00
24:00
hh:mm
545
Mo-Su: 3. Phase on
24:00
00:00
24:00
hh:mm
546
Mo-Su: 3. Phase off
24:00
00:00
24:00
hh:mm
556
Standard values
Su
Time program 4/TV
Parameter
Function
Production settings
Min.
Max.
Units
560
Preselection
Mo-Su
00:00
24:00
hh:mm
561
Mo-Su: 1. Phase on
6:00
00:00
24:00
hh:mm
562
Mo-Su: 1. Phase off
22:00
00:00
24:00
hh:mm
563
Mo-Su: 2. Phase on
24:00
00:00
24:00
hh:mm
564
Mo-Su: 2. Phase off
24:00
00:00
24:00
hh:mm
565
Mo-Su: 3. Phase on
24:00
00:00
24:00
hh:mm
566
Mo-Su: 3. Phase off
24:00
00:00
24:00
hh:mm
576
Standard values
Su
Time program 5
Parameter
Function
Production settings
Min.
Max.
Units
600
Preselection
Mo-Su
00:00
24:00
hh:mm
601
Mo-Su: 1. Phase on
6:00
00:00
24:00
hh:mm
602
Mo-Su: 1. Phase off
22:00
00:00
24:00
hh:mm
603
Mo-Su: 2. Phase on
24:00
00:00
24:00
hh:mm
604
Mo-Su: 2. Phase off
24:00
00:00
24:00
hh:mm
605
Mo-Su: 3. Phase on
24:00
00:00
24:00
hh:mm
606
Mo-Su: 3. Phase off
24:00
00:00
24:00
hh:mm
616
Standard values
Su
Holidays TO1
Parameter
Function
Production settings
Min.
Max.
Units
641
Preselection
1
8
-
642
Start
-
01.01
31.12.
dd.MM
643
End
-
01.01
31.12.
dd.MM
648
Type of operation
Anti-frost protection
Anti-frost protection,
Dumping
hh:mm
Holidays
selected type of operation Heating for the period of long-term absence. The function is activated on
the date, set in the parameter 642, and is ended in 00:00 hour on the date, set in the parameter
643.
Holidays TO2 (only in a case, that it is activated)
Parameter
Function
Production settings
Min.
Max.
Units
651
Preselection
1
8
-
652
Start
-
01.01
31.12.
dd.MM
653
End
-
01.01
31.12.
dd.MM
658
Type of operation
Anti-frost protection
Anti-frost protection,
Dumping
hh:mm