background image

 

5

 

Boiler Installation 

 

Important Cautions: 
Boiler  Installation  may  be  carried  out  exclusively  by  contractual  arrangement  with  approved  and  manufacturer’s 
accredited service organization 

Connections for heating and return water are situated always on one side of the boiler, right or left, in conformance to 
the space disposition of the boiler room.  

 

 

Installation of the gas manifold to pedestal equipped with cover sheet metal for combustion chamber 

 

Fastening boiler body to the pedestal. 

 

Installation of the horizontal draught interrupter onto the boiler body 

 

Installation of tubing for heating and return water with distributor pipe 

 

Burner installation 

 

Connecting gas armature with the burner 

 

Thermal insulation of the boiler body 

 

Partial jacketing of the boiler 

 

Mounting the electrical panel 

 

Carrying out the electrical installation 

 

Electrical conduit connections, placement of sensors, affixing manometer detecting sensor 

 

Electrical interconnection of the gas manifold 

 

Completion of the boiler jacketing 

 

2.1 

Pedestal Installation 

 

List of parts needed 

 

1 pc  

of boiler pedestal  

1 pc  

cover for the combustion chamber  

 

Installation procedure 

 

Position the cover sheet metal over future combustion 
chamber on the pedestal  

 

 

 

 

2.2 

Binding of the Boiler Body 

Using  800  kPa  (8  bar)  testing  overpressure  over  at  least  15  minutes,  test  the  integrity  of  the  boiler  assembly.  Visual  control  to  be 
carried out AFTER this test period. 

 
List of parts needed 

 

Boiler links  
1 pc  

boiler link left 

1 pc  

boiler link right 

8, 10; 13 pc  

of  middle  links,  number  is  determined  by  size 
of the boiler 

18, 22; 28 pc  

boiler inserts – as per boiler size 

3 pc  

anchoring screws M 10 x L  
(as per respective size) 

1 pc  

mounting brace 

2 pcs  

cover sheet metal lid 

6 pc  

of washer Ø 10 

1 pc  

of completed boiler pedestal 

4 pc  

of bolt M 8 

4 pc  

of nut M 8 

4 pc  

of washer Ø 8 

6 pc  

of nut M 10 

Oil or varnish colour for painting of the boiler inserts 
Boiler binder sealant 

 
Installation procedure 

 

1. 

All  sockets  and  drilled  socket  holes  in  boiler  links  must  be  thoroughly  cleaned  from 
conservation agents leftovers.  

2. 

Outer edges of the openings to be removed by a half-circular file. 

3. 

Paint the holes and sockets by oil or varnish paint. 

4. 

Deposit boiler glue paste on prepared cleanly grinded off surfaces of the links joint 

5. 

Tightening  of  the  boiler  body  parts  to  be  done  on  the  prepared  pedestal  with  cover  sheet 
metal  installed  such  that  the  combustion  chamber  is  directed  towards  the  front  part  of  the 
pedestal Inserts to be evenly deposited into the socket holes, using a light tap of the rubber 
or wooden mallet. 

6. 

Affix  the  boiler  link  over  the  protruding  inserts,  tap  in  place  and  carry  out  binding  of  the link 
with  aid  of  the  bonding  tools;  this  step  to  be  repeated  until  final  size  is  tightened  together 
Tightening is to be done by hydraulic or manual fastening clamps 

7. 

It is not permitted to tighten more than one link at a time.  

8. 

Boiler  links  to  be  pulled  together  evenly  both  on  the  upper  as  well  as  lower  level. 
Always keep ensuring that the links are installed parallel to each other. 
Using anchoring 
bolts, secure in place. Anchor nuts should be tightened only lightly (when tapping the bolt by 
a metal device, the sound must never be jingly). This is to allow dilatation of the boiler body 
when thermally stressed. 

cover sheet 
metal – burning 
space 
 
boiler pedestal 
 

Содержание G 90 10

Страница 1: ...VIADRUS G 90 Manual for assembly of boiler GB_ _ND 2015_26 GB_2017_23 ND...

Страница 2: ...al Panel installation 9 3 1 Installation of the Distributing Box 9 3 1 1 Electrical Panel installation 10 3 1 2 Completion of the Electrical Installation 10 3 2 Version 10 12 15 links automatics HONEY...

Страница 3: ...x kW 71 87 105 127 Rated thermal output min kW 55 61 73 94 Volume gas flow at the maximum thermal output m3 h 1 7 16 9 25 11 32 13 61 Volume gas flow at the minimum thermal output m3 h 1 5 56 6 5 7 85...

Страница 4: ...4 Number of sections 8 10 12 15 L mm 995 1155 1315 1555 L1 mm 815 975 1135 1375 A mm 878 5 941 941 941 D mm 200 200 225 250 Gas inlet...

Страница 5: ...boiler 18 22 28 pc boiler inserts as per boiler size 3 pc anchoring screws M 10 x L as per respective size 1 pc mounting brace 2 pcs cover sheet metal lid 6 pc of washer 10 1 pc of completed boiler p...

Страница 6: ...1 1 2 mount a complete distribution tube Into the threads G in the lower part of both end sections screw the outlet and inlet cocks Screw the cover sheet of the combustion chamber to the backside of...

Страница 7: ...sheet metal screws Note at the 8 section the horizontal draught diverter is compact Installation of the horizontal draught interrupter 2 5 Installation of burner List of parts needed 1 pc burner comp...

Страница 8: ...left side of the support in front fasten the side part of shell A left 2 into the riveting nut by means of 1 screw M5 and screw together by means of self drilling screws 4 2 with already fastened sid...

Страница 9: ...on a side portion of the jacket left cover B Above a smaller console shall be installed to assist in securing the terminals 2 Sequentially 8 pc of entry bushing PG11 to be mounted on the distribution...

Страница 10: ...nd piece of the tube PG 48 1 pc End piece of the tube PG 36 1 pc Nut of the end piece of the tube PG 36 Installation procedure 1 End pieces of the tubes PG36 and PG48 are to be fastened into the elect...

Страница 11: ...x 7 Further line wires No 10 11 15 22 27 28 45 and 55 are connected to the ionization automatics 8 The remaining line wires put through the end piece of the protective tube PG48 and then the actual tu...

Страница 12: ...6 1 pc Nut of the end piece of the tube PG 36 450 mm Protection tube PG 36 1 pc Ionization automatics HONEYWELL S 4563B1011 2 pcs Screw AM4 x 8 1 pc Bundle of conduits Installation procedure 1 With ai...

Страница 13: ...ody 6 Cable cover tube PG36 should be fastened into end pieces situated on the Distribution Box and the Electrical Panel Console 3 3 3 Completion of the Electrical Installation List of parts needed 1...

Страница 14: ...tion electrode F1 Fuse 4 A F2 Fuse 2 5 A H1 Signalling Boiler under voltage H2 failure signalling H3 ionising failure signalling S1 Main power switch S2 Reduced rated output switch S3 Pushbutton RESET...

Страница 15: ...on box A1 Automatics Honeywell 4563B1011 F1 Fuse 4 A X10 Boiler s terminal plate Y1 Gas Valve Honeywell VR4601QB 2001 Z1 Anti interference element PS3 Minimal water level guard SP1 Minimal gas pressur...

Страница 16: ...electrode F2 Fuse 2 5 A H1 Signalling Boiler under voltage H2 failure signalling H3 ionising failure signalling S1 Main power switch S2 Reduced rated output switch S3 Pushbutton RESET BT1 safety therm...

Страница 17: ...signalling H3 ionising failure signalling S1 Main power switch S2 Reduced rated output switch S3 Pushbutton RESET X10 Boiler s terminal plate Y1 Gas Valve Honeywell VR4601QB 2001 Y2 Gas Valve Honeywe...

Страница 18: ...eywell 4563B1011 F1 Fuse 4 A X10 Boiler s terminal plate Y1 Gas Valve Honeywell VR4601QB 2001 Y2 Gas Valve Honeywell VR4605QB 2002 Z1 Anti interference element PS3 Minimal water level guard SP1 Minima...

Страница 19: ...ion electrode F2 Fuse 2 5 A H1 Signalling Boiler under voltage H2 failure signalling H3 ionising failure signalling S1 Main power switch S2 Reduced rated output switch S3 Pushbutton RESET BT1 safety t...

Страница 20: ...ge H2 failure signalling H3 ionising failure signalling S1 Main power switch S2 Reduced rated output switch S3 Pushbutton RESET X10 Boiler s terminal plate Y1 Gas Valve Dungs MB ZRDLE 412B01S22 Z1 Ant...

Страница 21: ...utomatics Honeywell 4563B1011 F1 Fuse 4 A X10 Boiler s terminal plate Y1 Gas Valve Dungs MB ZRDLE 412B01S22 Z1 Anti interference element PS3 Minimal water level guard SP1 Minimal gas pressure guard SP...

Страница 22: ...oduct innovation these might not be included in this Manual hereto presented E1 Ignition electrode E2 Small burner ionization electrode E3 Burner ionization electrode F2 Fuse 2 5 A H1 Signalling Boile...

Страница 23: ......

Страница 24: ...VIADRUS G 90 VIADRUS a s Bezru ova 300 E mail CZ 735 81 Bohum n info viadrus cz www viadrus cz...

Отзывы: