background image

02/2017

 

www.vgebv.nl

 

7/18

 

Manual for: 

VGE Pro UV Control  400/420/600 and VGE Pro UV Control  140/200    

EP600001, EP200002 

 

 

 

3     Important safety notes

 

 

Make sure, that all of the following safety rules are fulfilled.

 

 

The device must only be installed by qualified personnel to make sure all applicable safety rules are fulfilled. 

Additional safety rules and legal restrictions may apply depending on the country of operation.

 

• 

Risk of electric shock!

 

Lethal high voltage is present inside the unit and at the terminals. Due to high voltage storage devices lethal voltages 
may be present inside the unit and at the terminals if the unit is switched off or disconnected from supply voltage. 

• The unit must not be operated if there is any damage (e.g. mechanical damage after transport). 
• The unit is intended for use in dry and chemically and biologically inactive environment only. Keep water and humidity 

away from the whole electrical assembly. Lethal voltages across the complete system can result from contact 
between lamp and water. A separate protective earthing of the complete system is mandatory. 

• Disconnect unit from mains before any maintenance operation. 

Dangerous voltage may be present inside the unit energy storage devices even if the unit is disconnected from mains. 
Wait at least 10 minutes after disconnecting the unit from mains voltage before starting any service actions. 

• Repeated rapid switching might lead to a fault. Do not turn off and on the unit within less than 10 seconds. 
• During ballast section start up, in case of lamp defects or due to wrong lamp wiring high voltages up to 1200V

eff  

may 

occur at the lamp terminals. This high voltage may be present for a couple of milliseconds until the internal protection 
circuits shuts down the ballast. At each ballast restart, after any temporary disconnection from mains voltage, the 
ballast will try to ignite the lamp once more, so again, high voltages may occur. 

• The ballast does not provide galvanic insulation from mains at the lamp terminals. 
• Harmful voltage occurs at the lamp terminals even if the ballast is in standby mode and the lamps are switched off. 
• Never cut the lamp wires while the ballast is in operation. 

Risk of serious injury or death!

 

• The load for the fault detecting contacts has to be kept within the limits specified in the datasheet. It is recommended 

to use parallel operation of contacts instead of serial operation in case of summarizing fault detection. 

• 

The insulated contacts of the status relays do not provide protection against electric shock.

 

All wires of the error control loop have to be installed with appropriate protection against contact according to 
applicable regulations. The wires of the error control loop must never be accessed from outside the earthed cabinet 
without protection against contact. You may use insulation relays to access the control loop from outside the cabinet.

Содержание EP200002

Страница 1: ...ture monitoring digital UV temperature sensors UV photodiode sensor KTY temperature sensor remote start and status monitoring remote start input Interlock mains switch 3 relay contacts 4 20mA signal input output manufacturer VGE International B V Ekkersrijt 4304 5692DH Son name of product VGE Pro UV Control Monitor 420 600 and VGE Pro UV Control Monitor 140 200 article code EP600001 EP200002 suita...

Страница 2: ...W mains 230 V AC 0 C 32 F 55 C 131 F ballast heat sink temperature overheating shutdown on exceeding 80 C 176 F storage temperature 0 C 32 F 40 C 104 F cooling of unit forced cooling using integrated fan internal fan lagtime 1 min IP protection cabinet IP54 Altitude 2000 m above sea level operating position vertical lamp terminals at bottom lamp cable 4 wire cable length per lamp max 30 m Wiring s...

Страница 3: ...ens digital sensor terminal X7 1 12V DC supply 2 signal A 3 signal B 4 ground for signal supply UV UV diode sensor terminal X8 1 cathode 2 anode shield Iin current input terminal X9 1 12V DC supply 2 signal 3 ground for signal supply relay function depends on operating software potential free resistive load max current 8A at 250V AC 24V DC min current 10mA at 5V max voltage 250C AC 80V DC Note Whe...

Страница 4: ...rent 1mA at loop resistance 0Ω loop resistance max 1kΩ 12V DC supply voltage output power max 1W not sustained short circuit proof short circuit current max 250mA max 10s Note The overall power consumption of switch 2 digisens and current input Iin must not exceed 1 5W otherwhile the unit will be switched off automatically interface to control panel connection using CAT5e patch cable includes powe...

Страница 5: ...nel during operation mains voltage monitoring during preheating during ignition during lamp operation turn off all lamps if mains voltage too low or too high brownout blackout detection during preheating turn off all lamps detection during lamp operation restart lamps without preheating if brownout blackout duration is below max value overheating protection during preheating during ignition during...

Страница 6: ...vollständige Einhaltung folgender Normen Compliance of the designated products with directive specifications is confirmed and proved by complete adherence of the following standards EN 61000 6 2 2005 Fachgrundnormen Störfestigkeit für Industriebereiche AC 2005 Generic standards Immunity for industrial environments EN 61000 3 2 2006 Grenzwerte Grenzwerte für Oberschwingungsströme A1 2009 A2 2009 Li...

Страница 7: ...s voltage before starting any service actions Repeated rapid switching might lead to a fault Do not turn off and on the unit within less than 10 seconds During ballast section start up in case of lamp defects or due to wrong lamp wiring high voltages up to 1200Veff may occur at the lamp terminals This high voltage may be present for a couple of milliseconds until the internal protection circuits s...

Страница 8: ...brown 2 white 3 blue 4 black X8 UV diode sensor terminal 1 blue 2 black X9 current input terminal including 12V DC supply for external module X10 current output terminal X11 temperature sensor terminal including ground connector for cable shield X12 RS485 terminal modbus including ground connector for cable shield X13 Flow switch 2 terminal including 12V DC supply for external module function depe...

Страница 9: ...ull out the cable gently the terminal should not allow the wire to move RS485 communication cable routing Use twisted pair shielded cable for communication wiring connect shield to the central earth point Do not cross RS485 communication cables and mains or lamp cables If this is unavoidable cross the cables at right angles as far apart as possible in order to reduce high frequency coupling Do not...

Страница 10: ...he control panel frontend Depending on operation software selected operation states can be signalised via relay 1 4 A number of status LEDs directly at the base unit give additional status information lamp status LEDs S1 red ON lamp fault blinking in start up sequence only if auto restart is activated green ON lamp on blinking preheating both LEDs OFF lamp off ballast status LED S3 ballas on yello...

Страница 11: ... the cursor use buttons UP DOWN and RIGHT LEFT Power the system Switch on main switch or connect power plug à system remains in standby mode Switching ON the system Press button RIGHT to enter the System ON OFF menu Move in menu to system on by button DOWN and press button ENTER to start lamp operation à The UV lamps will be operated with its nominal operation parameter Systemstatusindication fron...

Страница 12: ...urred clock info screen 1 UV value if UV sensor is present info screen 2 Temperature of frontend board Temperature of the ballasts on base board External Temperature if external temperature sensor is present Info screen 3 actual lamp current and lamp power of all lamps Info screen 4 Lamp hour counter Lamp switch on cycle counter Remaining lamp lifetime The number of info screens may vary depending...

Страница 13: ...ributor for lamp details An appropriate measuring technique is needed to determine the impact on the lamp if ballast settings are changed Note use this feature to adjust the system to the actual operation conditions e g environment temperature Installation and configuration of digital UV Sensor to be specified see Settings submenu overview main menu à settings à UV sensor Installation and configur...

Страница 14: ...or messages e g lamp error this menu will be left automatically UVhold This function will freeze the measured UV value on display The function is required for drinking water applications for reference checks according to DVGW or OENORM Note The function is only available if a digital UV sensor is present UV lamps are operating and warm up time is expired The UV hold function will be left automatic...

Страница 15: ...r of failed lamps allowed to be off before giving an alarm If less or equal number of lamps are defective as set in this menu the system will generate a lamp warning event and set the warning relay If more lamps are off than specified here the system will reset the operation relay and generate a lamp error event max lamprestarts default 3 A number of restarts can be allowed if a lamp cannot be ign...

Страница 16: ...V value is not been checked for warning or alarm state during this warm up time Note a lamp re ignition attempt causes a restart of the warm up delay timer shortwarmuptime default N No If enabled the warm up time is shortened to 30 sec if a UV sensor is activated and the UV values of all UV sensors are above their warning thresholds restartdelay default 240 sec set the restart delay 5 3600 sec Thi...

Страница 17: ...ve UV value of all sensors connected warnvalue default 80W m UV warning threshold for activating warning relay on base unit and yellow LED warning on frontend alarmvalue default 60W m UV alarm threshold for activating alarm relay on base unit and red LED alarm on frontend calibrationfactor default 100 adjust the displayed UV value on deviations from a reference sensor address enter submenu for set...

Страница 18: ... UV alarm main menu à settings à temperature contains all system settings for internal and external temperature measurement as well as warning and alarm delays exit Exit menu externaltemp external temperature sensor setup type alarm warning thresholds cool down to threshold internaltemp internal temperature sensor setup warning threshold warndelay default 60 sec set appropriate delay alarmdelay de...

Отзывы: