background image

02/2017

 

www.vgebv.nl

 

9/18

 

Manual for: 

VGE Pro UV Control  400/420/600 and VGE Pro UV Control  140/200    

EP600001, EP200002 

 

 

 

 

• The unit may only be wired according to the wiring diagram shown here. 
• Do not add any components such as switches, capacitors or ignition devices to the wires between ballast and lamp 

because this may damage the ballast. 

• Make sure that all wires are sufficiently insulated with respect to each other and to earth. 

 

 

• Wire gauge and length are specified according to connector manufacturers general data. Make sure that the actual 

wire size complies with the current electrical specifications. 

• The terminals are designed to clamp rigid and flexible wires without wire termination. If wire termination is used it must 

comply with the appropriate terminal specification. 

• Rigid wiring: 

- may be inserted directly into the terminals without pressing the release lever if specified wire gauge is used 

• Flexible wiring (braid wires): 

- may only be inserted direct into the terminals by pressing the release lever on the terminal 
- may not be soldered/tinned (This applies especially to screw terminals. The solder migrates into the contact, 

resulting in less reliable connection.) 

- wire end ferrules may be used, although not necessary 

• Make sure that the terminals are properly connected. 
• Check wiring for secure connection. This is advisable especially after mechanical stress such as transportation. 

To check the wiring at the terminal try to pull out the cable gently; the terminal should not allow the wire to move. 

 

RS485 communication cable routing

 

• Use twisted pair (shielded) cable for communication wiring, connect shield to the central earth point. 
• Do not cross RS485 communication cables and mains or lamp cables. If this is unavoidable, cross the cables at right 

angles as far apart as possible in order to reduce high frequency coupling. 

• Do not route RS485 communication cables and mains or lamp cables parallel or close to each other. 

Keep them as far apart as possible from each other (minimum: 5-10 cm) to avoid radio interference between leads. 

 

 

Lamp/Mains cable routing

 

• Do not cross mains and lamp cables. If this is unavoidable, cross the cables at right angles as far apart as possible in 

order to reduce high frequency coupling. 

• Do not route mains cables and lamp cables parallel or close to each other. 

Keep them as far apart as possible from each other (minimum: 5-10 cm) to avoid radio interference between mains 
and lamps leads. 

• Route a separate wire with size of 4mm² that is connected to earth in parallel to the lamp wires to reduce radiated 

emissions at lamp wires. Do not use multi-core cables with integrated protective earth wires. 

• Use one cable per lamp. 

 

 

Lamp/Mains cable length

 

• Keep mains cable short to reduce radio interference. 
• Keep the lamp cables as short as possible to reduce electromagnetic interferences and to minimise parasitic 

capacitances. 

• When considering the max. lamp cable length, all cables inside the cabinet and inside the reactor/channel must be 

included. 

• Selection of cable types and layout should be made with respect to the lowest coupling capacity and inductance.

Содержание EP200002

Страница 1: ...ture monitoring digital UV temperature sensors UV photodiode sensor KTY temperature sensor remote start and status monitoring remote start input Interlock mains switch 3 relay contacts 4 20mA signal input output manufacturer VGE International B V Ekkersrijt 4304 5692DH Son name of product VGE Pro UV Control Monitor 420 600 and VGE Pro UV Control Monitor 140 200 article code EP600001 EP200002 suita...

Страница 2: ...W mains 230 V AC 0 C 32 F 55 C 131 F ballast heat sink temperature overheating shutdown on exceeding 80 C 176 F storage temperature 0 C 32 F 40 C 104 F cooling of unit forced cooling using integrated fan internal fan lagtime 1 min IP protection cabinet IP54 Altitude 2000 m above sea level operating position vertical lamp terminals at bottom lamp cable 4 wire cable length per lamp max 30 m Wiring s...

Страница 3: ...ens digital sensor terminal X7 1 12V DC supply 2 signal A 3 signal B 4 ground for signal supply UV UV diode sensor terminal X8 1 cathode 2 anode shield Iin current input terminal X9 1 12V DC supply 2 signal 3 ground for signal supply relay function depends on operating software potential free resistive load max current 8A at 250V AC 24V DC min current 10mA at 5V max voltage 250C AC 80V DC Note Whe...

Страница 4: ...rent 1mA at loop resistance 0Ω loop resistance max 1kΩ 12V DC supply voltage output power max 1W not sustained short circuit proof short circuit current max 250mA max 10s Note The overall power consumption of switch 2 digisens and current input Iin must not exceed 1 5W otherwhile the unit will be switched off automatically interface to control panel connection using CAT5e patch cable includes powe...

Страница 5: ...nel during operation mains voltage monitoring during preheating during ignition during lamp operation turn off all lamps if mains voltage too low or too high brownout blackout detection during preheating turn off all lamps detection during lamp operation restart lamps without preheating if brownout blackout duration is below max value overheating protection during preheating during ignition during...

Страница 6: ...vollständige Einhaltung folgender Normen Compliance of the designated products with directive specifications is confirmed and proved by complete adherence of the following standards EN 61000 6 2 2005 Fachgrundnormen Störfestigkeit für Industriebereiche AC 2005 Generic standards Immunity for industrial environments EN 61000 3 2 2006 Grenzwerte Grenzwerte für Oberschwingungsströme A1 2009 A2 2009 Li...

Страница 7: ...s voltage before starting any service actions Repeated rapid switching might lead to a fault Do not turn off and on the unit within less than 10 seconds During ballast section start up in case of lamp defects or due to wrong lamp wiring high voltages up to 1200Veff may occur at the lamp terminals This high voltage may be present for a couple of milliseconds until the internal protection circuits s...

Страница 8: ...brown 2 white 3 blue 4 black X8 UV diode sensor terminal 1 blue 2 black X9 current input terminal including 12V DC supply for external module X10 current output terminal X11 temperature sensor terminal including ground connector for cable shield X12 RS485 terminal modbus including ground connector for cable shield X13 Flow switch 2 terminal including 12V DC supply for external module function depe...

Страница 9: ...ull out the cable gently the terminal should not allow the wire to move RS485 communication cable routing Use twisted pair shielded cable for communication wiring connect shield to the central earth point Do not cross RS485 communication cables and mains or lamp cables If this is unavoidable cross the cables at right angles as far apart as possible in order to reduce high frequency coupling Do not...

Страница 10: ...he control panel frontend Depending on operation software selected operation states can be signalised via relay 1 4 A number of status LEDs directly at the base unit give additional status information lamp status LEDs S1 red ON lamp fault blinking in start up sequence only if auto restart is activated green ON lamp on blinking preheating both LEDs OFF lamp off ballast status LED S3 ballas on yello...

Страница 11: ... the cursor use buttons UP DOWN and RIGHT LEFT Power the system Switch on main switch or connect power plug à system remains in standby mode Switching ON the system Press button RIGHT to enter the System ON OFF menu Move in menu to system on by button DOWN and press button ENTER to start lamp operation à The UV lamps will be operated with its nominal operation parameter Systemstatusindication fron...

Страница 12: ...urred clock info screen 1 UV value if UV sensor is present info screen 2 Temperature of frontend board Temperature of the ballasts on base board External Temperature if external temperature sensor is present Info screen 3 actual lamp current and lamp power of all lamps Info screen 4 Lamp hour counter Lamp switch on cycle counter Remaining lamp lifetime The number of info screens may vary depending...

Страница 13: ...ributor for lamp details An appropriate measuring technique is needed to determine the impact on the lamp if ballast settings are changed Note use this feature to adjust the system to the actual operation conditions e g environment temperature Installation and configuration of digital UV Sensor to be specified see Settings submenu overview main menu à settings à UV sensor Installation and configur...

Страница 14: ...or messages e g lamp error this menu will be left automatically UVhold This function will freeze the measured UV value on display The function is required for drinking water applications for reference checks according to DVGW or OENORM Note The function is only available if a digital UV sensor is present UV lamps are operating and warm up time is expired The UV hold function will be left automatic...

Страница 15: ...r of failed lamps allowed to be off before giving an alarm If less or equal number of lamps are defective as set in this menu the system will generate a lamp warning event and set the warning relay If more lamps are off than specified here the system will reset the operation relay and generate a lamp error event max lamprestarts default 3 A number of restarts can be allowed if a lamp cannot be ign...

Страница 16: ...V value is not been checked for warning or alarm state during this warm up time Note a lamp re ignition attempt causes a restart of the warm up delay timer shortwarmuptime default N No If enabled the warm up time is shortened to 30 sec if a UV sensor is activated and the UV values of all UV sensors are above their warning thresholds restartdelay default 240 sec set the restart delay 5 3600 sec Thi...

Страница 17: ...ve UV value of all sensors connected warnvalue default 80W m UV warning threshold for activating warning relay on base unit and yellow LED warning on frontend alarmvalue default 60W m UV alarm threshold for activating alarm relay on base unit and red LED alarm on frontend calibrationfactor default 100 adjust the displayed UV value on deviations from a reference sensor address enter submenu for set...

Страница 18: ... UV alarm main menu à settings à temperature contains all system settings for internal and external temperature measurement as well as warning and alarm delays exit Exit menu externaltemp external temperature sensor setup type alarm warning thresholds cool down to threshold internaltemp internal temperature sensor setup warning threshold warndelay default 60 sec set appropriate delay alarmdelay de...

Отзывы: