VESDA
®
LaserSCANNER Product Manual
7
Alarm Levels
ALERT: When lit this LED indicates that the smoke
level is above the alert threshold. This means the
detector has identified very early stages of a fire
condition and/or that the smoke level in the area is
above normal.
ACTION: When lit this LED indicates that the detected
smoke level has passed the threshold value fixed for
Action, but is not intended to initiate a general fire alarm
response procedure.
FIRE 1: When lit this LED indicates that the detected
smoke level is above the threshold value set to initiate
a general fire alarm response procedure. This
indicates a fire may be imminent or is in progress.
When interfaced with a Fire Alarm Control Panel
(FACP) it can generate an automatic fire alarm.
FIRE 2: When lit this LED indicates a fire is in progress. The detector can be
interfaced with an FACP to activate automatic suppression systems and
evacuation procedures.
Bar graph
The Bar graph is a 20 step indicator where each indicator represents an
increase in the detected level of smoke, relative to the preset fire alarm level.
Threshold
Indicators
The illuminated LEDs represent visual settings for ALERT, ACTION, and FIRE
1 alarm levels. The FIRE 1 indicator is always at the top.
Fault LEDs
The Fault LEDs illuminate to indicate:
URGENT: A serious fault requiring immediate attention
SYSTEM: A fault affecting the network to which the Display module is
connected
ZONE: A fault in the VESDA Zone monitored by the Display module
POWER: A fault in the power supply if the GPI function is used
NETWORK: A communications fault on VESDAnet
AIRFLOW: Higher or lower than acceptable levels of air flow through the inlet
pipe(s)
FILTER: The air filter requires changing