1.12 Maintaining the VESDA LaserSCANNER
To maintain the VESDA LaserSCANNER at its peak performance the maintenance schedule
given below should be followed. Maintenance can be conducted by the original installer, a
VESDA distributor, a service contractor. To work effectively the LaserSCANNER detector
needs to be supported by a well designed Pipe Network. The Maintenance Schedule includes
the maintenance required for the Pipe Network. Given below is a suggested Maintenance
Schedule for the LaserSCANNER detector. Local codes and standards, and site conditions take
precedence in preparing a Maintenance Schedule.
Table 7 - Suggested maintenance schedule for LaserSCANNER detector
Caution:
While a VESDA Zone is isolated for maintenance, no fire warnings will be issued by
the detector and any fire will go undetected. Prior to any maintenance or testing:
Inform appropriate supervising authority about the risk associated with isolating a
VESDA Zone.
Check to see if the detector is also being used by third party.
Ensure that any ancillary devices dependent on the LaserSCANNER detector are
enabled by the isolation before work is begun.
Maintenance Check
Quarterly
Six
Monthly
Annual
Every Two
Years
Power Supply
D
Check Pipe Network
D
Filter Inspection
D
Pipe Integrity Smoke Test
D
Check Pipe Flow
D
Clean Sampling Points
D
Flush Pipe Network
D