VESDA
®
LaserSCANNER Product Manual
15
Default Settings
Parameter
Default Value
Range
Access
Level
Minimum
Maximum
Airflow Delay
0 seconds
0
60 seconds
Adm
•
High Urgent
130%
105%
200%
Adm
•
High Minor
120%
105%
200%
Adm
•
Low Minor
80%
25%
95%
Adm
•
Low Urgent
70%
25%
95%
Adm
Aspirator Speed
3,000 rpm
3,000 rpm
4,200 rpm
Adm
AutoLearn
14 days
0 Hours
0 Minutes
0 Days
0 Hours
15 minutes
15 days
23 Hours
59 Minutes
Adm
Adm
Adm
Display Mode
Smoke level
NA
NA
Usr
Display Button
Lockout…Buttons
Enabled
NA
NA
Adm
Communications:
Open-ended loop
Preferred Port
Network Delay
Health Check
None
A
15 seconds
45 seconds
NA
10 seconds
40 seconds
NA
45 seconds
60 seconds
Adm
Dst
Dst
Dst
Day Start
07:00:00
NA
NA
Adm
Night Start
19:00:00
NA
NA
Adm
Device ID
Name & Number
NA
NA
Adm
Event Log to View
Smoke Level
Alarms
Faults
User Action
NA
NA
Adm
Adm
Adm
Adm
Faults Latched
Latched
NA
NA
Adm
Filter Service Interval
1825 days (5 years)
1 Day
1825 days (5
years) Normal
Environment
Adm
Alarms Latched
Latched
NA
NA
Adm
Alert Threshold
0.08% obs/m
0.025% obs/ft.
0.005% obs/m
0.0015% obs/ft.
1.99% obs/m
0.6218% obs/ft.
Adm
Action Threshold
0.14% obs/m
0.044% obs/ft.
0.010% obs/m
0.0031 obs/ft.
1.995% obs/m
(0.6234 obs/ft.
Adm