LaserSCANNER Product Manual
VESDA
®
32
Replacing the chassis/Air Inlet Pipe Manifold
1.
Isolate the LaserSCANNER by pressing the
Isolate
button or by selecting
Isolate Zone
from the
Zone
menu in VConfig Pro or VSM3. This isolates the outputs from the unit to a
fire alarm panel and other third party devices such as building management systems.
2.
If you are using VConfig Pro or VSM3, highlight the detector in the Device Tree Window and
select the
Device
menu, then
Save Node Configuration.
This will save the configuration
details of the LaserSCANNER.
3.
Remove the front panel by using a flat ended screw driver to open the cover plate (A) and
screw covers (B), then unscrew the front cover.
Figure 22 - Removing Front Cover
4.
Either let the front cover hang on the plastic retainer straps, or take it off by disconnecting
the retainer straps and the termination cable loom where it connects to the front cover (C).
5.
Turn off the power by disconnecting the power cables. Power terminals can be seen on
The
terminal card
on page 25.
6.
Unscrew the PCB head processor card (D), lift up and disconnect the
flow sensor
(E) and
scanner
(F) cables from the card.
Figure 23 - Remove Data cables
7.
On the terminal card, disconnect the
Termination
and
Relays
cables. For details see
The
terminal card
on page 25.
A
B
Legend
A
Cover plate screws
B
Screw covers
Legend
C
Termination cable
D
Head processor card
E
Flow sensor cable
F
Scanner cable
C
D
E
F