background image

14

ORIGINAL INSTRUCTIONS

VES  Andover  Ltd  Eagle  Close  Chandlers  Ford  Ind.  Est  Eastleigh  Hampshire  SO53  4NF
Tel:  08448  156060    Fax:  02380  261204    E-mail:  [email protected]  Web:  www.ves.co.uk

Heat Recovery Unit

Installation,  Operation  and  Maintenance  Manual

®

Maintainance

6

Continued

To replace the fan assembly, ensuring the pitot
tapping on the fan inlet ring is accessible, locate
the mounting plate over the fixings retained in the
unit bulkhead. 

 

Secure the loose fixings

through the mounting plate and tighten all the
mounting fixings. 

 Attach the measuring tube to

the pitot tapping on the inlet ring ensuring that it
is clear of all moving parts. Reconnect the supply
plugs as in Fig. 

; if more than one plug is used,

ensure the correct plugs are reconnected as marked.
E

nsure that the fans are free running by following the fan alignment instructions on page 11, 

adjust as

required.

In  order  to  keep  the  unit  in  good  order  the  following  maintenance  routine  is  recommended:

Filters  should  be  inspected  every  three  months.  If  they  are  found  to  be  heavily  soiled  or  damaged
in  any  way  they  should  be  replaced.  Spare  filters  can  be  ordered  from  VES  Spares  Department.

The  fan  impeller  should  be  cleaned  every  6  months.  Failure  to  clean  the  fan  on  a  regular  basis
could  result  in  loss  of  fan  performance,  or  cause  it  to  fall  out  of  balance.  If  a  fan  is  stationary  for
long  periods  in  a  humid  atmosphere,  it  should  be  switched  ON  for  minimum  of  two  hours  every
month  to  remove  any  moisture  that  may  have  condensed  within  the  motor.
The  fan  motors  are  maintenance  free  due  to  the  use  of  ball  bearings  with  “life-long  lubrication”.
At  the  end  of  the  grease  life  it  will  be  necessary  to  change  the  bearings  or  change  the  fan  unit.  The
life  expectancy  of  bearings  for  standard  usage  is  approximately  30  -  40000  hours.
If  included,  backdraught  shutters  should  be  free  moving  and  unobstructed.  Check  the  foam  seals
and  replace  as  necessary.  Backdraught  assemblies  are  available  as  a  spare  part  if  required.
Failure  to  keep  dampers  clean  could  result  in  the  damper  becoming  inoperative.  Clean  damper
blades  and  frames  and  lubricate  with  PTFE  aerosol  or  equivalent.
The  heat  exchanger  matrix  should  be  inspected  for  debris,  dust  or  dirt  build  up.  If  found
contaminated,  foreign  matter  should  be  removed  accordingly;  superficial  dust  or  debris  can  be
removed  from  the  surface  of  the  heat  exchange  by  gently  brushing.  Loosened  debris  can  then  be
vacuumed  from  the  surface  of  the  matrix  or  flushed  through  with  warm  water.  Stubborn  deposits  can
be  removed  by  using  a  low  pressure  washer  with  an  approved  detergent  solution.  The  solution
temperature  should  not  exceed  50°C.  When  using  any  pressure  device  care  must  be  taken  not  to
damage  the  heat  exchanger  matrix.

Under  NO  circumstances  should  the  heat  exchanger  be  steam  cleaned.

Ensure  the  drain  pan  and  the  drain  connection  is  free  from  debris  ensuring  any  condensate
produced  can  freely  drain  away.  Should  a  full  service  be  required  it  may  be  necessary  to
disassemble  the  unit  casework  to  gain  access  to  some  components.

Ecovent® 

EVX 

units  are  supplied  with  both  unpainted  galvanised  sheet  steel  cases  and  powder

coat  paint  finish.  Check  all  painted  items  to  ensure  that  they  have  not  deteriorated,  particularly
where  adverse    environmental  conditions  prevail.  Re-paint  as  necessary.  Matching  paint  can  be
supplied  upon  request.

When  enquiring  after  or  ordering  spares  contact  VES  Spares  Department,  quoting  the  sales  order
(SO)  number  and  unit  type  as  found  on  the  unit  nameplate.

Tel: 08448 15 60 60 • Fax: 02380 26 12 04

At the end of their useful life the packaging and product should be disposed of via a suitable recycling
centre. Do not dispose of with normal household waste. Do not burn.

PLEASE ENSURE THAT THIS DOCUMENT IS PASSED ON TO THE END USER

We  reserve  the  right  to  alter  the  specifcation  without  notice  ©VES  Andover  Ltd.  2012.
No part of this publication may be photocopied or otherwise reproduced without the prior permission in
writing of VES Andover Ltd.

Three Monthly Checks

Six Monthly Checks

Twelve Monthly Checks

Spares & Repairs

WEEE Directive

Caution

Recommended Checks

Fan assembly removal/

installation

Fig.

Содержание ecovent

Страница 1: ...s of reference Indicates hazards associated with electric current and high voltages Indicates hazards that require safety advice for personnel or potential unit property damage Indicates important inf...

Страница 2: ...ing Null No Heating E Electric Heater Battery W LPHW Coil 9 Infill DS 25mm double skinned acoustic infill EE 50mm double skinned EN1886 standard 10 Handing LT Left Top Access denotes position of RT Ri...

Страница 3: ...eful consideration must be paid to the location of the unit in relation to the ductwork and associated items placing the unit directly adjacent to a bend in ductwork will impede airflow and reduce per...

Страница 4: ...ularly important with twin extract fan units as this may otherwise cause the backdraught flaps to operate incorrectly Unit mounting detail Fig Installation 4 Important On EVX E units an electric heate...

Страница 5: ...ainst damage from extreme weather conditions during the winter season If the water is allowed to freeze in the coil system damage may occur potentially bursting pipes and resulting in emergency proble...

Страница 6: ...n codes of practice and if fitted upstream to steam or water coils care must be taken to ensure that the air temperature does not drop below 0 C For units supplied with condensing units refer to the a...

Страница 7: ...omer s responsibility to supply earth fault protection through the building installation device and a dedicated isolated power supply with overload protection to account for motor start up currents Se...

Страница 8: ...143 Fig Continued PE N L1 1 200 277 V 50 Hz J3 J2 J1 PE N L1 E1 Analog In A1 Tacho Out OC GND 10 V DC Out GNYE BU BN YE WH BU RD 10 k External speed setting Input 0 10 V N L1 PE Line 1 200 277 V 50 Hz...

Страница 9: ...for Ecovent EVX447 Fig Continued 24V 10VGND D1 E1 11 14 DC Out I max 70 mA DC Out I max 10 mA Digital In 1 Analog In 1 N L1 PE L1 L2 L3 PE L1 N K1 Contact rating max AC 250 V 2 A Input 0 10 V Ex tting...

Страница 10: ...Hz DC 24 V BK OR RD WH Y U 1 3 2 5 DC 0 10 V NOT USED T CM24 SR NM24A SR Damper Actuator To isolate from the main power supply the system must incorporate a device which disconnects all the phase con...

Страница 11: ...further operational details The centrifugal fans have infinite speed adjustment the benefits of real energy savings are apparent when the fan speed is reduced this is best demonstrated when used in c...

Страница 12: ...ifferential pressure 550Pa Unit EVX616 Reading from graph 1 0 Air Volume 1 0m s 700 750 800 850 900 950 1000 1050 1100 1150 1200 0 50 100 150 200 250 300 350 400 450 500 550 600 650 0 0 1 0 2 0 3 0 4...

Страница 13: ...For bottom access units should it be necessary to remove the heat exchanger from the unit casework take care to ensure that all components are correctly supported during their removal Remove the lids...

Страница 14: ...required Failure to keep dampers clean could result in the damper becoming inoperative Clean damper blades and frames and lubricate with PTFE aerosol or equivalent The heat exchanger matrix should be...

Страница 15: ...X Heat Recovery Unit Type EVX Manufacturer VES Andover Limited The product above is produced in accordance with EC Council Directives 2004 108 EC Electromagnetic Compatibility Directive 2006 95 EC Low...

Страница 16: ...nty 12 24 months from the date of dispatch This can be covered at a cost of just 3 of order value minimum charge 50 00 Option 3 12 36 Month Extended Warranty 12 36 months from date of dispatch For thi...

Отзывы: