background image

13

ORIGINAL INSTRUCTIONS

VES  Andover  Ltd  Eagle  Close  Chandlers  Ford  Ind.  Est  Eastleigh  Hampshire  SO53  4NF
Tel:  08448  156060    Fax:  02380  261204    E-mail:  [email protected]  Web:  www.ves.co.uk

Heat Recovery Unit

Installation,  Operation  and  Maintenance  Manual

®

Important

Warning

Caution

Maintainance

6

Before attempting to carry out any work on our units, all accompanying documentation including warning
labels on the unit must be referenced.
Should it be necessary to remove any component ensure that these are secured into position once
reinstalled. It is critical that after any maintenance work has been conducted that all components
removed/replaced be refitted correctly by a competent engineer.

Before attempting to carry out any maintenance work, investigative or repair work on our units, the unit

MUST BE COMPLETELY ISOLATED 

from its electrical supply. Ensure a minimum of two minutes after

electrical disconnection before removing access panels. This will allow any moving parts to come to a rest.
Care should also be taken when accessing external units as the wind and elements may cause moving
parts to ‘windmill’.

In general, this series of units require little maintenance. In the unlikely event of component failure, spares
are available from stock at VES Andover Ltd.

When accessing the unit ensure the access panels are handled/opened in a controlled manner so as to
avoid damage to the unit or injury to personnel. This is particularly important with bottom access units.
Ensure the AHU has been allowed to completely cool before attempting any work to the unit

For bottom access units, should it be necessary to remove the heat exchanger from the unit casework take
care to ensure that all components are correctly supported during their removal.
Remove the lids and central mullion from the unit, exposing the bypass damper. As an additional safety
measure some components are held into place using PK screws as shown.
Remove the required components with care and ensure all components are replaced correctly.

All  Ecovent® 

EVX

  units  feature  plug  &  socket  connections  to  allow  easy  removal/replacement  of

key  components.  Separate  the  plug  connection  by  hand  (tools  not  required)  by  lifting  the

locking  lever 

  and  pulling  the  plug/socket  apart 

DO  NOT

  pull  the  cable  to  separate  the

assembly.

On reconnection, the assembly features a locating lug to ensure correct orientation. Once rejoined ,lock
the connection together again using the locking lever as shown.

Ecovent®

  EVX 

units  1  to  5  feature  a  bulkhead-mounted  fan  plate  assembly.

Ensure that special care is taken when removing/replacing components/assemblies from bottom-access
units. For larger components this may require the use of two or more persons.
The mounting plate is slotted to aid plate alignment. It is important to keep the fan assembly supported at
all times; the fan assembly should not be considered supported until all fixings are securely tightened.

To remove the fan assembly Fig.

, ensure the unit is fully isolated. Separate the supply plugs to the fan

as shown above 

 Detach the measuring tube from the inlet ring and stow the tube clear .

 Back-out the bottom screws but do not remove . 

 Remove the top fixings completely and retain .

Carefully lift the fan assembly over the retained fixings and remove the fan assembly from the unit.

Important

Plug & socket operation

Fig.

Содержание ecovent

Страница 1: ...s of reference Indicates hazards associated with electric current and high voltages Indicates hazards that require safety advice for personnel or potential unit property damage Indicates important inf...

Страница 2: ...ing Null No Heating E Electric Heater Battery W LPHW Coil 9 Infill DS 25mm double skinned acoustic infill EE 50mm double skinned EN1886 standard 10 Handing LT Left Top Access denotes position of RT Ri...

Страница 3: ...eful consideration must be paid to the location of the unit in relation to the ductwork and associated items placing the unit directly adjacent to a bend in ductwork will impede airflow and reduce per...

Страница 4: ...ularly important with twin extract fan units as this may otherwise cause the backdraught flaps to operate incorrectly Unit mounting detail Fig Installation 4 Important On EVX E units an electric heate...

Страница 5: ...ainst damage from extreme weather conditions during the winter season If the water is allowed to freeze in the coil system damage may occur potentially bursting pipes and resulting in emergency proble...

Страница 6: ...n codes of practice and if fitted upstream to steam or water coils care must be taken to ensure that the air temperature does not drop below 0 C For units supplied with condensing units refer to the a...

Страница 7: ...omer s responsibility to supply earth fault protection through the building installation device and a dedicated isolated power supply with overload protection to account for motor start up currents Se...

Страница 8: ...143 Fig Continued PE N L1 1 200 277 V 50 Hz J3 J2 J1 PE N L1 E1 Analog In A1 Tacho Out OC GND 10 V DC Out GNYE BU BN YE WH BU RD 10 k External speed setting Input 0 10 V N L1 PE Line 1 200 277 V 50 Hz...

Страница 9: ...for Ecovent EVX447 Fig Continued 24V 10VGND D1 E1 11 14 DC Out I max 70 mA DC Out I max 10 mA Digital In 1 Analog In 1 N L1 PE L1 L2 L3 PE L1 N K1 Contact rating max AC 250 V 2 A Input 0 10 V Ex tting...

Страница 10: ...Hz DC 24 V BK OR RD WH Y U 1 3 2 5 DC 0 10 V NOT USED T CM24 SR NM24A SR Damper Actuator To isolate from the main power supply the system must incorporate a device which disconnects all the phase con...

Страница 11: ...further operational details The centrifugal fans have infinite speed adjustment the benefits of real energy savings are apparent when the fan speed is reduced this is best demonstrated when used in c...

Страница 12: ...ifferential pressure 550Pa Unit EVX616 Reading from graph 1 0 Air Volume 1 0m s 700 750 800 850 900 950 1000 1050 1100 1150 1200 0 50 100 150 200 250 300 350 400 450 500 550 600 650 0 0 1 0 2 0 3 0 4...

Страница 13: ...For bottom access units should it be necessary to remove the heat exchanger from the unit casework take care to ensure that all components are correctly supported during their removal Remove the lids...

Страница 14: ...required Failure to keep dampers clean could result in the damper becoming inoperative Clean damper blades and frames and lubricate with PTFE aerosol or equivalent The heat exchanger matrix should be...

Страница 15: ...X Heat Recovery Unit Type EVX Manufacturer VES Andover Limited The product above is produced in accordance with EC Council Directives 2004 108 EC Electromagnetic Compatibility Directive 2006 95 EC Low...

Страница 16: ...nty 12 24 months from the date of dispatch This can be covered at a cost of just 3 of order value minimum charge 50 00 Option 3 12 36 Month Extended Warranty 12 36 months from date of dispatch For thi...

Отзывы: