background image

5

ORIGINAL INSTRUCTIONS

VES  Andover  Ltd  Eagle  Close  Chandlers  Ford  Ind.  Est  Eastleigh  Hampshire  SO53  4NF
Tel:  08448  156060    Fax:  02380  261204    E-mail:  [email protected]  Web:  www.ves.co.uk

Heat Recovery Unit

Installation,  Operation  and  Maintenance  Manual

®

Continued

A  drain  pan  is  fitted  to  all  units.  Should  conditions  mean  that  condensation  is  likely  ensure
that  the  unit  connected  to  an  appropriate  waste  system.  Refer  to  manual  VES  Ref.  ID665  for
further  information  on  trapping  details.
Consideration  should  be  given  to  the  height  required  for  the  trap  to  function  correctly  and  that
the  unit  may  need  additional  base  support  in  order  to  accommodate  this  correctly.
For  EVX  units  1  -  5  an  optional  peristaltic  pump  is  available.  For  pump  fitting  and  installation
instructions  see  the  documentation  accompanying  the  pump  assembly.
The  drain  pan  is  fitted  with  an  internal  spigot  suitable  for  connection  with  a  push-fit  straight
connector,  to  be  supplied  by  others  (EVX  1  -  5  Ø15  mm,  6  -  8  Ø22  mm).  Terminate  through  the
case  onsite  as  required,  ensuring  that  any  swarf  is  removed.  Should  it  be  required  to  remove
any  component,  ensure  that  it  is  replaced  correctly.

Coils  should  be  piped  according  to  any  relevant  local  codes  of  practice.  Where  threaded
connections  are  supplied,  the  only  approved  method  of  jointing  method  is  by  use  of  Boss  white
and  hemp.  The  thread  fitted  to  the  coil  is  to  be  supported  at  all  times  whilst  making  joints.  All
external  piping  is  to  be  supported  independently  from  the  coil.  Fluid  filters  are  recommended.

It  is  important  that  water  and  steam  coils  are  protected  against  damage  from  extreme  weather
conditions  during  the  winter  season.  If  the  water  is  allowed  to  freeze  in  the  coil  system,
damage  may  occur  potentially  bursting  pipes  and  resulting  in  emergency  problems.
Fitting  a  frost  thermostat  at  the  unit  inlet  and  ensuring  that  boilers  run  continuously  in  low
ambient  temperatures  can  help  to  prevent  this.

Heating  coils  do  not  cool  immediately  when  the  hot  water  supply  is  cut  off.  The  residual  heat
must  be  dissipated  to  avoid  damage.  The  continuous  running  of  the  fan  after  shutdown
resolves  this,  by  operation  of  a  run-on  timer.
The  recommended  length  of  run-on  is 

2  minutes  minimum

.

On  Ecovent® 

EVX  /  -W

  units,  a  Low  Pressure  Hot  Water  (LPHW)  coil  will  be  installed.  The  coils

are  normally  suitable  for  LPHW  at  82°C  flow  and  71°C  return  temperature.  LPHW  coils  are
supplied  as  standard  with  an  air  vent  and  drain  plug  located  on  the  pipe  work  immediately
adjacent  to  the  coil  connections  on  the  AHU.  The  air  vent  should  be  at  the  highest  point,  with
the  drain  at  the  lowest.  The  coil  should  be  regularly  vented  so  as  to  avoid  potential  air  locks,
resulting  in  a  fall  off  of  duty.
It  is  recommended  that  a  check  be  made  as  to  whether  any  treatment  is  required  to  the  water
supply  for  prevention  of  corrosion  and  scaling  of  the  equipment.  Information  regarding  the
necessary  action  to  be  taken  can  be  obtained  from  the  relevant  Local  Water  Supply  Authority.

The  unit  will  have  been  supplied  with  connections  either  left  or  right-hand  side  looking  in
direction  of  airflow.  Please  see  order  acknowledgement  for  confirmation  of  this  handing.
Should  you  need  to  alter  this  please  consult  VES  as  unit  adjustment  may  invalidate  your
warranty.

Installation

4

Caution

Typical LPHW Coil

Fig. 

Caution

Coils

LPHW Coils

Airflow

Flow

Return

Condensate Trapping

Содержание ecovent

Страница 1: ...s of reference Indicates hazards associated with electric current and high voltages Indicates hazards that require safety advice for personnel or potential unit property damage Indicates important inf...

Страница 2: ...ing Null No Heating E Electric Heater Battery W LPHW Coil 9 Infill DS 25mm double skinned acoustic infill EE 50mm double skinned EN1886 standard 10 Handing LT Left Top Access denotes position of RT Ri...

Страница 3: ...eful consideration must be paid to the location of the unit in relation to the ductwork and associated items placing the unit directly adjacent to a bend in ductwork will impede airflow and reduce per...

Страница 4: ...ularly important with twin extract fan units as this may otherwise cause the backdraught flaps to operate incorrectly Unit mounting detail Fig Installation 4 Important On EVX E units an electric heate...

Страница 5: ...ainst damage from extreme weather conditions during the winter season If the water is allowed to freeze in the coil system damage may occur potentially bursting pipes and resulting in emergency proble...

Страница 6: ...n codes of practice and if fitted upstream to steam or water coils care must be taken to ensure that the air temperature does not drop below 0 C For units supplied with condensing units refer to the a...

Страница 7: ...omer s responsibility to supply earth fault protection through the building installation device and a dedicated isolated power supply with overload protection to account for motor start up currents Se...

Страница 8: ...143 Fig Continued PE N L1 1 200 277 V 50 Hz J3 J2 J1 PE N L1 E1 Analog In A1 Tacho Out OC GND 10 V DC Out GNYE BU BN YE WH BU RD 10 k External speed setting Input 0 10 V N L1 PE Line 1 200 277 V 50 Hz...

Страница 9: ...for Ecovent EVX447 Fig Continued 24V 10VGND D1 E1 11 14 DC Out I max 70 mA DC Out I max 10 mA Digital In 1 Analog In 1 N L1 PE L1 L2 L3 PE L1 N K1 Contact rating max AC 250 V 2 A Input 0 10 V Ex tting...

Страница 10: ...Hz DC 24 V BK OR RD WH Y U 1 3 2 5 DC 0 10 V NOT USED T CM24 SR NM24A SR Damper Actuator To isolate from the main power supply the system must incorporate a device which disconnects all the phase con...

Страница 11: ...further operational details The centrifugal fans have infinite speed adjustment the benefits of real energy savings are apparent when the fan speed is reduced this is best demonstrated when used in c...

Страница 12: ...ifferential pressure 550Pa Unit EVX616 Reading from graph 1 0 Air Volume 1 0m s 700 750 800 850 900 950 1000 1050 1100 1150 1200 0 50 100 150 200 250 300 350 400 450 500 550 600 650 0 0 1 0 2 0 3 0 4...

Страница 13: ...For bottom access units should it be necessary to remove the heat exchanger from the unit casework take care to ensure that all components are correctly supported during their removal Remove the lids...

Страница 14: ...required Failure to keep dampers clean could result in the damper becoming inoperative Clean damper blades and frames and lubricate with PTFE aerosol or equivalent The heat exchanger matrix should be...

Страница 15: ...X Heat Recovery Unit Type EVX Manufacturer VES Andover Limited The product above is produced in accordance with EC Council Directives 2004 108 EC Electromagnetic Compatibility Directive 2006 95 EC Low...

Страница 16: ...nty 12 24 months from the date of dispatch This can be covered at a cost of just 3 of order value minimum charge 50 00 Option 3 12 36 Month Extended Warranty 12 36 months from date of dispatch For thi...

Отзывы: