NetSure -48V DC Bulk Output Power System Installation and User Instructions (UM582127100)
|
Rev. E
41
-48V DC Output Connections
Important Safety Instructions
DANGER!
Adhere to the “Important Safety Instructions” presented at the front of this document.
ALERT!
Observe proper polarity when making output connections.
Recommended Torques
•
300 in-lbs for 3/8-inch hardware (when using standard flat and lock washer).
•
180 in-lbs for 3/8-inch hardware (when using a Belleville lock washer).
General
DC output leads are connected to the output busbars located on the back of the rectifier shelves. These
busbars provide 3/8” clearance holes for installation of customer-provided two hole lugs that have 1 inch
centers and 3/8 inch bolt clearance holes. Customer must order or provide lug mounting hardware.
You connect DC output leads per a single rectifier shelf in the system or for pairs of rectifier shelves in the
system (depending on how many shelves are in the system). Refer to
DC output cables can either enter from the right, from the left, or from the rear. The shelf should have been
configured for your installation site per the “Changing the Direction of the DC Output Cables” procedure on
page 15. Refer to
for typical lug layout diagrams.
After making DC output connections, re-install any rear shield removed in “Mounting the Rectifier Module
Mounting Shelf(s) to a Relay Rack” on page 14.