LEVEL
SETTINGS
DEFAULT
VALUE
UNITS
MODELS
AFFECTED
NOTES
SWOTP Delay
10
seconds
C,R
Delay required for persistent over-temperature alarm
condition before SWOTP triggered.
SWOTP Scope
Local
—
C,R
Local = affects only PDU connected to the temperature
sensor that triggered SWOTP.
Array = affects all PDUs regardless of temperature
sensor that triggered SWOTP.
Criticality
Critical
—
C,R
Affects power control when a member of a receptacle
group.
Locked/Unlocked
Unlocked
—
C,R
Affects authorization to manage power control and
behavior of SWOCP.
4.3.4 Determine IP Address, MAC Address and Firmware Version
1. Use the arrow keys to highlight the Information icon and press the
Select
key.
2. Use the arrow key to highlight the Network icon and press the
Select
key to view the IP
address, MAC address, firmware, time and date.
Figure 4.10 IP address, MAC address and Firmware Information Example
NUMBER
DESCRIPTION
1
IP address
2
MAC address
3
Agent firmware type and version
NOTE: The preceding illustration is an example of network information.
4.3.5 Adjust the Contrast of the On-board LCD
NOTE: Contrast adjustment may help improve display legibility in a high-temperature environment.
The on-board display is factory-set to be easily viewed in lighting conditions found in most work places,
however the contrast can be changed to suit user preference.
1. Press any key to activate the display.
2. Use the arrow keys to highlight the Information icon, and press the
Select
key.
3. Use the arrow keys to highlight the Contrast icon, and press the
Select
key.
Vertiv
| Vertiv™ MPH2 Rack PDU Installer/User Guide
31
Содержание MPH2
Страница 1: ...Vertiv MPH2 Rack PDU Installer User Guide ...
Страница 16: ...Vertiv Vertiv MPH2 Rack PDU Installer User Guide 12 This page intentionally left blank ...
Страница 42: ...Vertiv Vertiv MPH2 Rack PDU Installer User Guide 38 This page intentionally left blank ...
Страница 48: ...Vertiv Vertiv MPH2 Rack PDU Installer User Guide 44 This page intentionally left blank ...
Страница 49: ......