LEVEL
SETTINGS
DEFAULT
VALUE
UNITS
MODELS
AFFECTED
NOTES
PDU
User Assigned Label
MPH2™
Rack PDU
or
Rack PDU
<alpha>
—
All
RackPDU is default value the first time only.
Allowed characters include alphanumeric, space,
and ~!#$_+`-={}|[]\\:;'?,.\/%^&*()@
Asset Tag 1
<empty>
—
All
Asset Tag 2
<empty>
—
All
Overcurrent Alarm
Threshold
45
%
All
% calculated from maximum input-current rating on
nameplate.
Default values are recommended for dual-corded server
applications.
Overcurrent Warning
Threshold
40
%
All
Undercurrent Alarm
Threshold
0
%
All
Unbalanced Load Alarm
threshold
0
%
All 3-phase
% difference calculated between any two phases.
Software Over Current
Protection (SWOCP)
Disabled
—
R
Conditionally applies to unlocked and unloaded receptacles
only.
Branch
User Assigned Label
Branch
<alpha>
—
All
Allowed characters include alphanumeric, space,
and ~!#$_+`-={}|[]\\:;'?,.\/%^&*()@
Asset Tag 1
<empty>
—
All
Asset Tag 2
<empty>
—
All
Overcurrent Alarm
Threshold
95
%
All
% calculated from CB rating. Refer to nameplate for
maximum branch current rating.
Overcurrent Warning
Threshold
90
%
All
Undercurrent Alarm
Threshold
0
%
All
SWOCP
Disabled
—
R
Conditionally applies to all unlocked and unloaded
receptacles only for this branch.
Receptacle
User Assigned Label
Receptacle
<number>
—
All
Allowed characters include alphanumeric, space,
and ~!#$_+`-={}|[]\\:;'?,.\/%^&*()@
Asset Tag 1
<empty>
—
All
Asset Tag 2
<empty>
—
All
Overcurrent Alarm
Threshold
95
%
M,R
Configurable per receptacle.
% calculated from maximum receptacle current rating on
nameplate.
Overcurrent Warning
Threshold
90
%
M,R
Undercurrent Alarm
Threshold
0
%
M,R
Power Up State
Restore
—
C,R
Restore returns receptacle power state to last
programmed state after expiration of Power On Delay.
Power On Delay
0
seconds
C,R
The delay timing begins after measurement stability is
achieved.
Power Cycle Delay
8
seconds
C,R
A Power Cycle turns off power to the receptacle for the
specified delay.
Post On Delay
0
seconds
C,R
Delay before RPC2 issues command to power on
receptacle.
Post Off Delay
0
seconds
C,R
Delay before RPC2 issues command to power off
receptacle.
Software Over Temperature
Protection (SWOTP)
Disabled
—
C,R
Unconditionally applies regardless of locked/unlocked and
loaded/unloaded status.
At least one temperature sensor is required.
Table 4.1 Factory-default settings
Vertiv
| Vertiv™ MPH2 Rack PDU Installer/User Guide
30
Содержание MPH2
Страница 1: ...Vertiv MPH2 Rack PDU Installer User Guide ...
Страница 16: ...Vertiv Vertiv MPH2 Rack PDU Installer User Guide 12 This page intentionally left blank ...
Страница 42: ...Vertiv Vertiv MPH2 Rack PDU Installer User Guide 38 This page intentionally left blank ...
Страница 48: ...Vertiv Vertiv MPH2 Rack PDU Installer User Guide 44 This page intentionally left blank ...
Страница 49: ......