![Vertiv Liebert RX Скачать руководство пользователя страница 32](http://html.mh-extra.com/html/vertiv/liebert-rx/liebert-rx_user-manual_1008069032.webp)
Vertiv
| Liebert
®
RX
™
Remote Distribution Cabinet User Manual |
28
5.0
MAINTENANCE
5.1
Repair
Even the most reliable equipment may fail. Vertiv is at your service to assure fast repair of your
unit and minimum down-time of your installation.
Standard electrical troubleshooting procedures should be used to isolate problems in the unit. If
there are questions, don’t hesitate to contact Vertiv.
Repair or replacement of standard items, such as circuit breakers and fuses can be either handled
by qualified electricians or referred to Vertiv.
Repairs related to the monitoring system should be referred to Vertiv.
To contact Vertiv for information or repair service in the USA, call 1-800-543-2378.
5.2
Inspection & Cleaning
Air circulation through the cabinet may cause dust to accumulate on internal components.
Cleaning should be done as necessary during electrical inspections.
Annual general system inspections, cleaning and operation checks are recommended to ensure
system performance and long service life.
5.2.1
Inspection Schedule
•
It is difficult to establish a schedule for periodic cleaning because conditions vary from site to site.
Inspections after the first 24 hours, after 30 days and after 6 months of operation should help determine a
pattern for the inspection schedule.
•
Electrical connections and component mountings should be inspected after the first 24 hours, after
30 days and after 6 months of operation. Inspections should be conducted annually thereafter.
•
Ventilation openings and grilles should be inspected and cleaned every 6 months to one year.
•
A complete inspection and operational checkout should be performed annually. This is best done by
performing the inspection and startup procedure as detailed in
3.0 - Inspection and Startup Checklist
.
•
Vertiv offers a complete range of preventive maintenance services. These include thorough equipment
performance checks and calibration of electronics. Contact Vertiv in the USA (1-800-543-2378) for
details.
WARNING
Risk of electric shock. May cause personal injury or death.
Only properly trained and qualified service personnel wearing appropriate safety headgear,
gloves, shoes and glasses should perform maintenance on the Liebert RX. All voltage
sources to the unit must be disconnected before inspecting or cleaning within the cabinet.
WARNING
Risk of electric shock. May cause personal injury or death.
Only properly trained and qualified service personnel wearing appropriate safety headgear,
gloves, shoes and glasses should perform maintenance on the Liebert RX. All voltage
sources to the unit must be disconnected before inspecting or cleaning within the cabinet.