Figure 6
Electrical field connections for units with LDMF monitoring
Cut the wire ties and remove
the CT's. Run the input phase,
ground and neutral cables
through the CT's and secure
to the cable with wire ties. Install
the CT on the cable with the
white dot facing the source
for the phase connectors
and facing the load for the ground
and neutral.
Ground
Busbar
Neutral
Busbar
Input Ground Connection
5/16-18 x 1.5" Stud
Input Neutral Connection
See Detail A
Input Power Connection
Mechanical lug for
(2) 3/0-500kCMIL
Distribution Cable Conduit
Plate; 56 knockouts, each Ø 0.875"
for 1/2" conduit and 28 knockouts,
each Ø 1.125" for 3/4" Conduit
84-Pole
Distribution
Panelboard
Distribution Cable
Conduit Plate
84 knockouts, each Ø 0.875"
for 1/2" conduit
LDMF
LDMF Current
Sensors
Main Input
Circuit Breaker
DETAIL A
DETAIL B
(See drawings LDM13004 and
LDM13008 for connection details.)
Ø 0.563
(14.29mm)
4 Places
0.75"
(19.1mm)
1.75"
(44mm)
0.89" (23mm)
1.22" (31mm)
See Detail B
RX15000
Rev. 3