![Vertiv Liebert RX Скачать руководство пользователя страница 20](http://html.mh-extra.com/html/vertiv/liebert-rx/liebert-rx_user-manual_1008069020.webp)
Vertiv
| Liebert
®
RX
™
Remote Distribution Cabinet User Manual |
16
1.8
Current Plus Monitoring—Optional
If Current Plus Monitoring (CPM) is supplied, remote communications and summary alarm
connections are available.
A Liebert IntelliSlot
™
card provides connection to a Building Management System (BMS) or
Liebert SiteScan
®
monitoring interface. The following cards are available:
•
IS-WEBS card for SNMP/Web output to Ethernet LAN
•
IS-485S card for Modbus 485 output using a two-wire connection
•
IS-IPBMS card for Modbus IP output using an RJ-45 connection
•
IS-UNITY-DP card for HTTP/HTTPS, Vertiv Protocol, e-mail, SMS, SNMP v1/v2c/v3, BACnet IP/MSTP
and Modbus TCP/RTU output using a serial RS-485 two-wire connection
Check Liebert IntelliSlot slots on the back of the door to determine which card is supplied, more
than one card might be supplied. See
Figures 8
and
9
for location and connection details.
Figure 9
Current Plus Monitoring adapter board electrical field connections
1.8.1
Summary Alarm
Current Plus Monitoring provides a Form C (one NO and one NC) summary alarm contact for
remote alarm status. The summary alarm contacts change state upon occurrence of any alarm
including warnings and reset when the alarm is cleared. The summary alarm connection is on the
Adapter Board (see
Figure 8
, Detail A, and
Figure 11
) marked
Summary Alarm (NC) (NO)
and
(COMM)
. The contacts are rated at 24VAC at 1A.
NOTES:
1. The summary alarm contacts are rated
for 0 to 30VAC or VDC, 0.5A, 10 watts, maximum.
2. For Liebert SiteScan connection, use #22AWG
shielded cable; maximum distance: 1000ft (300m).
To Liebert
SiteScan
System
Summary
Alarm
LDM13011
Rev. 0
Shield
NC
NO
COM
Содержание Liebert RX
Страница 1: ...Liebert RX Remote Distribution Cabinet User Manual ...
Страница 33: ......