Vertiv
| Liebert
®
RX
™
Remote Distribution Cabinet User Manual |
18
Figure 10 Electrical field connections for CT Module replacement CTs
CONNECTION LOCATION FOR CT MODULE
6 REPLACEMENT CTs.
INDICATES PIN 1.
CONNECT CT WHITE WIRE TO PIN 1
CONNECT CT BLACK WIRE TO PIN 2
LOAD
PANELBOARD B
LDM13004
Rev. 0
NOTES:
1. REMOVE CT FROM THE BOX. ROUTE WIRING FROM
THE TRANSFORMER THROUGH THE PANEL TO THE
LDM CONTROL BOARD.
2. CONNECT THE CT CONNECTOR TO THE PROPER PANEL
LOCATION USING THE FIRST AVAILABLE CONNECTION:
A. FOR PANELBOARD A USE P2(A1), P3(A2), P4(A3)
B. FOR PANELBOARD B USE P5(B1), P6(B2), P7(B3)
ENSURE ALL ROUTED WIRING IS PROPERLY SECURED
TO THE PANEL WITH TIE WRAPS.
3. THE TOP PIECE OF THE CURRENT TRANSFORMER (CT)
IS REMOVABLE BY PULLING AWAY FROM THE CENTER
OF THE TRANSFORMER (ITEM 2).
4. PLACE THE MAIN BODY OF THE CURRENT
TRANSFORMER AROUND THE CABLE, MAKING SURE
THE CT IS INSTALLED IN THE DIRECTION SHOWN
(SEE ITEM 2).
5. REPLACE THE TOP PIECE OF THE CT TO COMPLETE
SECURING THE CT AROUND THE CABLE (SEE ITEM 3).
USE THE ENCLOSED TIE WRAPS TO SECURE THE CT
TO THE CABLE.
* WARNING: DO NOT OPEN CIRCUIT THE SECONDARY
WINDINGS OF CURRENT TRANSFORMERS. FAILURE
TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN
SERIOUS INJURY OR DEATH.
ITEM 3
ITEM 2
DETAIL A
PANELBOARD A
REPLACEMENT
CT (6 PL. TYP.)
BRANCH
CIRCUIT
POWER
SOURCE
POWER
SOURCE
LOAD
BRANCH
CIRCUIT