REV : 0
REV DATE : 11/18
DPN004864
Page :2 /3
CW305, 375, 415 DOWNFLOW MODELS
F
or
m
N
o.
: D
P
N
00
10
40
_R
E
V
4
ELECTRICAL FIELD CONNECTIONS
LIEBERT CW
OPTIONAL ELECTRICAL CONNECTIONS
9. Condensate alarm (with condensate pump option) - On pump high water indication, normally open dry
contact is closed across terminals 88 & 89 for remote indication. 1 AMP, 24VAC max load. Use Class 1
field supplied wiring.
10.
Remote humidifier - On any call for humidification, normally open dry contact is closed across terminals
11 & 12 to signal field supplied remote humidifier. 1 AMP, 24VAC max load. Use Class 1 field supplied
wiring
11.
Reverse Starter contacts - Normally open dry contact is closed across terminals 102 & 103 for power
supply 1 and 106 & 107 for power supply 2 to indicate the active power feed. 1 AMP, 24VAC max load.
Use Class 1 field supplied wiring.
12.
Smoke sensor alarm - Factory wired dry contacts from smoke sensor are 91-common, 92-NO, and 93-
NC. Supervised contacts, 80 & 81, open on sensor trouble indication. This smoke sensor is not intended
to function as, or replace, any room smoke detection system that may be required by local or national
codes. 1 AMP, 24VAC max load. Use Class 1 field supplied wiring.
13.
Analog inputs- Terminals 41, 42, 43, and 44 are user configurable for 0-10V, 0-5V, or 4-20MA.
OPTIONAL LOW VOLTAGE TERMINAL PACKAGE CONNECTIONS
14.
Remote unit shutdown - Two additional contact pairs available for unit shutdown (labeled as 37B & 38B,
37C & 38C). Replace jumpers with field supplied normally closed switch having a minimum 75VA, 24VAC
rating. Use field supplied Class 1 wiring.
15.
Common alarm - On any alarm, two additional normally open dry contacts are closed across terminals 94
& 95 and 96 & 97 for remote indication. 1 AMP, 24VAC max load. Use Class 1 field supplied wiring.
16.
Main fan enabled contact - On VFD enable, normally open dry contact is closed across terminals 84 & 85
for remote indication. 1 AMP, 24VAC max load. Use Class 1 field supplied wiring.
17.
LiquiTect shutdown and dry contact - On LiquiTect activation, normally open dry contact is closed across
terminals 58 & 59 for remote indication (LiquiTect sensor ordered separately). 1 AMP, 24VAC max load.
Use Class 1 field supplied wiring.
OPTIONAL COMMUNICATION CONNECTIONS
18.
Unit-to-Unit – Plug 64 is reserved for U2U communication
19.
Site and BMS – Plug 74 and terminal block 3 are reserved for Site and BMS connections. Plug 74 is an
eight pin RJ45 for a Cat 5 cable. Terminal block 3 is a two position screw terminal block for use with
twisted pair wires.
Содержание Liebert CW
Страница 1: ...Liebert CW Thermal Management System Installer User Guide 305 kW 375 kW 415 kW Capacity 50 60 Hz...
Страница 10: ...Vertiv Liebert CW Installer User Guide 6 This page intentionally left blank...
Страница 24: ...Vertiv Liebert CW Installer User Guide 20 This page intentionally left blank...
Страница 32: ...Vertiv Liebert CW Installer User Guide 28 This page intentionally left blank...
Страница 34: ...Vertiv Liebert CW Installer User Guide 30 This page intentionally left blank...
Страница 36: ...Vertiv Liebert CW Installer User Guide 32 This page intentionally left blank...
Страница 46: ...Vertiv Liebert CW Installer User Guide 42 This page intentionally left blank...
Страница 48: ...Vertiv Liebert CW Installer User Guide 44 This page intentionally left blank...
Страница 75: ...Vertiv Liebert CW Installer User Guide...