REV : 0
REV DATE : 11/18
DPN004864
Page :1 /3
CW305, 375, 415 DOWNFLOW MODELS
F
or
m
N
o.
: D
P
N
00
10
40
_R
E
V
4
ELECTRICAL FIELD CONNECTIONS
LIEBERT CW
STANDARD ELECTRICAL CONNECTIONS
1.
High voltage entrance - Located in bottom and top of box (quantity 2). Raceway in front left corner of
enclosure for routing high voltage wires thru enclosure.
2.
Low voltage entrance – Located in bottom and top of box (quantity 4). Raceway in front right corner of
enclosure for routing low voltage wires thru enclosure.
3.
Three phase electrical service - Terminals are on top of disconnect switch. Three phase service not
provided by Liebert.
4.
Earth ground - Terminal for field supplied earth grounding wire and component ground terminal strip.
Earth grounding required for Liebert units.
5.
Unit factory installed disconnect switch and Main Fuses – Access to the high voltage electric panel
compartment can be obtained only with the switch in the “off” position. Fused disconnects are provided
with a defeater button that allows access to the electrical panel when power is on.
6.
Remote unit shutdown - Replace existing jumper between terminals 37 & 38 with field supplied normally
closed switch having a minimum 75VA, 24VAC rating. Use field supplied Class 1 wiring.
7.
Customer alarm inputs - Terminals for field supplied, normally open contacts, having a minimum 75VA,
24VAC rating, between terminals 24 & 50, 51, 55, 56. Use field supplied Class 1 wiring. Terminal
availability varies by unit options.
8.
Common alarm - On any alarm, normally open dry contact is closed across terminals 75 & 76 for remote
indication. 1 AMP, 24VAC max load. Use Class 1 field supplied wiring.
Содержание Liebert CW
Страница 1: ...Liebert CW Thermal Management System Installer User Guide 305 kW 375 kW 415 kW Capacity 50 60 Hz...
Страница 10: ...Vertiv Liebert CW Installer User Guide 6 This page intentionally left blank...
Страница 24: ...Vertiv Liebert CW Installer User Guide 20 This page intentionally left blank...
Страница 32: ...Vertiv Liebert CW Installer User Guide 28 This page intentionally left blank...
Страница 34: ...Vertiv Liebert CW Installer User Guide 30 This page intentionally left blank...
Страница 36: ...Vertiv Liebert CW Installer User Guide 32 This page intentionally left blank...
Страница 46: ...Vertiv Liebert CW Installer User Guide 42 This page intentionally left blank...
Страница 48: ...Vertiv Liebert CW Installer User Guide 44 This page intentionally left blank...
Страница 75: ...Vertiv Liebert CW Installer User Guide...