8.1.1 Replacing the Filters
WARNING! Risk of contact with high-speed rotating fan blades. Can cause serious injury or
death. Open all local and remote electric power-supply disconnect switches, verify with a
voltmeter that power is off, and verify that all fan blades have stopped rotating before working
in the unit cabinet or on the fan assembly. If control voltage is applied, the fan motor can restart
without warning after a power failure. Do not operate the unit with any or all cabinet panels
removed.
1. The filters are accessed through panels on the front side of the plenum at the front of the unit,
see Figure 8.1 below.
Figure 8.1 Filter Access
Item
Description
1
Front access on the front side of the fan plenum.