Installation
Vertiv | Liebert CRD10 | User Manual
24
2.7
Operating and Storage Environment Conditions
In this section, take a look at the environmental conditions including the Operating and Storage environment.
2.7.1
Operating Condition
Table 2-4 defines the operating condition parameters including the ambient temperature, protection level,
altitude and voltage range.
Table 2-4 Operating Parameters
Item
Requirement
Ambient temperature
Indoor: Temperature 18°C (64.4F) to 40°C (104F), Relative humidity 17% to 60%
Outdoor: Temperature -15°C (5°F) to 45°C (113°F) without Low Ambient Kit
Temperature -34°C (-29.2°F) to 45°C (113°F) with Low Ambient Kit
Protection level
Indoor Unit: IP20, Outdoor Unit: IPX4
Altitude
< 2000m(6561.6ft.). Above that, please contact Vertiv
Operation voltage range
CRD100-0D00A
CRD101-0D00A
CRD102-1D00A
208/230V/1PH/60Hz
208/230V/3PH/60Hz
230V/1PH/50/60Hz
2.7.2
Storage Condition
Table 2-5 defines the Storage condition parameters including the ambient humidity, ambient temperature, and
storage time conditions.
Table 2-5 Storage Parameters
Item
Requirement
Storage environment
Indoor, clean (without dust)
Ambient humidity
< 95%RH @ 30°C(86F)
Ambient temperature
-40°C (-40F) to 70°C(158F)
Storage time
Total transportation and storage time should not exceed six months. Otherwise, the
performance needs to be re-calibrated
2.8
Weight Bearing Capacity
The CRD10 unit is installed on the floor of the computer room, Therefore, the weight bearing capacity of the
floor of the computer room must be taken into consideration.
If the weight bearing capacity cannot be estimated, consult Vertiv or the customer service/support center.