Maintenance & Troubleshooting
Vertiv | Liebert CRD10 | User Manual
98
7.8
Condensate pump maintenance
WARNING! Risk of electric shock. Can cause injury or death. Open all local and remote electric power-
supply disconnect switches and verify that power is Off with a voltmeter before working within the
condensate pump electrical connection enclosure. The Liebert® controller does not isolate power
from the unit, e
ven in the “Unit Off” mode. Some internal c
omponents require and receive power
even durin
g the “Unit Off”
mode of the Liebert® controller.
7.8.1
Pump Replacement:
1.
Disconnect the power to unit using disconnect switch.
2.
Open the rear door.
Figure 7-5 The Location of Condensate Pump
3.
Pull out pipe of the pump by unscrewing the hose clamp.
4.
Unscrew the hose clamp that was used to fix the pump.
Condensate pump