Chapter 3 Installation Drawing 29
LIEBERT APM UPS Module And Parallel System 30kVA~150kVA User Manual
Fig.
4-2:
External Battery Connections
•
Externa BCB interface UHW242C2
–
J6.1 DRV: BCB: Drive signal
–
J6.2 FB: BCB: Contact status
–
J6.3 GND: Ground
–
J6.4 OLBCB: Online-Input (normally open): This pin is active when BCB interface signal is connected.
•
BCB control board UHW242C2
–
Control and feedback X102 to J6, Bypass Module
–
External battery temperature, X108 to J8, Bypass Module
–
B/- supply to X101
–
UV coil and auxiliary to X100
–
Battery temperature sensors X103, X104, X105, X106