Components that can be maintained by user
All the equipment maintenance and servicing procedures involving internal access need special tools and should be carried
out only by trained personnel.The components that can only be accessed by opening the protective cover with tools cannot
be maintained by user.
This UPS full complies with “IEC62040-1 General and safety requirements for UPS”. Dangerous voltages are present within
the battery box. However, the risk of contact with these high voltages is minimized for non-service personnel.Since the
component with dangerous voltage can only be touched by opening the protective cover with a tool, the possibility of
touching high voltage component is minimized.No risk exists to any personnel when operating the equipment in the normal
manner, following the recommended operating procedures in this manual.
Battery voltage higher than 400Vdc
All the battery maintenance and servicing procedures involving internal access need special tools or keys and should be
carried out only by trained personnel.
SPECIAL CARE SHOULD BE TAKEN WHEN WORKING WITH THE BATTERIES ASSOCIATED WITH THIS EQUIPMENT.
WHEN CONNECTED TOGETHER, THE BATTERY TERMINAL VOLTAGE WILL EXCEED 400Vdc AND IS POTENTIALLY
LEATHAL.
Battery manufacturers supply details of the necessary precautions to be observed when working on, or in the vicinity of, a
large bank of battery cells. These precautions should be followed implicitly at all times. Particular attention should be paid to
the recommendations concerning local environmental conditions and the provision of protective clothing, first aid and
fire-fighting facilities.