2.5
Master-Slave-Modul
Technische Daten
– Nutzungsbeschränkung: Europa
– Nennspannung: max. 250 Vac
– Nennstrom, max. Betriebsstrom:
I
MASTER
+ I
SLAVE
(cos
ϕ
= 1): max. 16 A
I
MASTER
: 16 A–I
SLAVE
I
SLAVE
: 16 A–I
MASTER
I
SLAVE
(max)
(cos
ϕ
= 0,4): max. 8 A
(I
MASTER
< 8 A)
– Maximale Schaltleistung:
cos
ϕ
= 1: 4 000 VA
∼
,
cos
ϕ
= 0,4: 2 000 VA
∼
– Leistungsaufnahme (Leerlauf):
< 2 W (230 V)
– Einschaltstrom: 55 mA ± 5 %
(Werkeinstellung)
– Ausschaltstrom: 44 mA ± 5 %
(Werkeinstellung)
– Einschaltverzögerung: 550 ms
(I
MASTER
> 1,15 x I
EINSCHALT
): ± 20 % (230 V)
– Ausschaltverzögerung: 550 ms
(I
MASTER
< 0,7 x I
AUSSCHALT
): ± 20 % (230 V)
– Einschaltstrom-Einstellbereich:
20…200 mA
– Temperaturbereich: 0…50 °C
– Relative Luftfeuchtigkeit: 10 ... 90 %
Funktion
– Nach Einschalten des Master-Gerätes
an der schwarzen Steckdose schalten
die Slave-Steckdosen mit einer halben
Sekunde Verzögerung.
– Sind die Slave-Geräte eingeschaltet,
können sie durch das Einschalten des
Masters in Betrieb genommen werden.
– Durch Ausschalten des Master-Gerätes
werden auch alle Slave-Geräte vom Netz
getrennt.
Schaltschwelle einstellen
Schalten die Slave-Geräte nach Inbetrieb-
nahme des Masters nicht ein, Schwellwert
herabsetzen.
– Mastergerät einschalten und sicher-
stellen, dass die Slave-Geräte betriebs -
gereit, d. h. eingeschaltet sind.
– Einstellschraube langsam nach
rechts drehen, bis das Relais der
Steckdosenleiste schaltet und die Slave-
Geräte mit Strom versorgt.
– Gegenprobe: Master-Gerät ausschalten.
Die Slave-Geräte müssen selbsttätig
ausschalten.
– Schalten die Slave-Geräte nach dem
Ausschalten des Masters nicht aus:
Schwellwert erhöhen.
– Master-Gerät ein- und, nachdem die
Slave-Geräte alle aktiviert sind, wieder
ausschalten.
– Einstellschraube langsam nach
links drehen, bis das Relais der
Steckdosenleiste abschaltet und die
Slave-Geräte stromlos sind.
Master-slave module
Technical data
– Usage restriction: Europe
– Nominal voltage: max. 250 Vac
– Nominal current, Max. operating current:
I
MASTER
+ I
SLAVE
(cos
ϕ
= 1): max. 16 A
I
MASTER
: 16 A–I
SLAVE
I
SLAVE
: 16 A–I
MASTER
I
SLAVE
(max)
(cos
ϕ
= 0.4): max. 8 A
(I
MASTER
< 8 A)
– Max. contact rating:
cos
ϕ
= 1: 4 000 VA
∼
,
cos
ϕ
= 0.4: 2 000 VA
∼
– Power consumption (idle): < 2 W (230 V)
– Switch-on current: 55 mA ± 5 %
(factory setting)
– Switch-off current: 44 mA ± 5 %
(factory setting)
– Switch-on delay: 550 ms
(I
MASTER
> 1.15 x I
SWITCH-ON
): ± 20 % (230 V)
– Switch-off delay: 550 ms
(I
MASTER
< 0.7 x I
SWITCH-OFF
): ± 20 % (230 V)
– Switch-on current setting range: 20…200 mA
– Temperature range: 0…50 °C
– Relative humidity: 10 ... 90 %
Function
– After the master unit has been switched on
(on the black socket) the slave sockets switch
on with a half second delay.
– Once the slave units have been switched on
they are ready for use by switching on the
master.
– If the master unit is switched off, all slave units
are also disconnected from the mains.
Setting the switching threshold
If the slave units do not switch on after the mas-
ter has been switched on: Reduce the threshold.
– Switch on the master unit and ensure that the
slave units are in standby mode, i. e. switched
on.
– Slowly turn the adjustment screw clockwise
until the relay on the socket strip switches on
and power is supplied to the slave units.
– Reverse test: Switch off master unit.
The slave units must switch off auto matically.
– If the slave units do not switch off once the
master has been switched off: Increase the
threshold.
– Switch master unit on, and once the slave units
have all been activated, switch it back off.
– Slowly turn the adjustment screw anti-
clockwise until the relay on the socket strip
switches off and no further current is supplied
to the slave units.
Module Master Slave
Caractéristiques techniques
– Restriction d’usage : Europe
– Tension nominale : max. 250 Vac
– Intensité nominale, courant de service max. :
I
MASTER
+ I
SLAVE
(cos
ϕ
= 1) : max. 16 A
I
MASTER
: 16 A–I
SLAVE
I
SLAVE
: 16 A–I
MASTER
I
SLAVE
(max)
(cos
ϕ
= 0,4) : max. 8 A
(I
MASTER
< 8 A)
– Puissance d’interruption maximale :
cos
ϕ
= 1 : 4 000 VA
∼
,
cos
ϕ
= 0,4 : 2 000 VA
∼
– Consommation (marche à vide) :
< 2 W (230 V)
– Courant de démarrage : 55 mA ± 5 %
(réglage en usine)
– Courant de coupure :44 mA ± 5 %
(réglage en usine)
– Temporisation d’enclenchement : 550 ms
(I
MASTER
>1,15 x I
ENCLENCHEMENT
) : ± 20 % (230 V)
– Temporisation de mise hors servie : 550 ms
(I
MASTER
<0,7 x I
MISE HORS SERVICE
) : ± 20 % (230 V)
– Plage de réglage du courant de fermeture :
20…200 mA
– Plage de températures : 0…50 °C
– Humidité de l’air relative : 10 ... 90 %
Fonction
– Après mise en marche de l’appareil Master (au
niveau de la prise noire), les prises Slave com-
mutent au bout d’une demi seconde.
– Si les appareils Slave sont enclenchés, ils
peuvent être mis en service par l’enclenchement
du Master.
– En éteignant l’appareil Master, tous les appareils
Slave sont également coupés du réseau.
Régler le seuil de commutation
Si les appareils Slave ne se mettent pas
en marche après la mise en service du Master :
abaisser le seuil de commutation.
– Allumer l’appareil Master et s’assurer
que les appareils Slave sont prêts à fonctionner,
c’est-à-dire qu’ils sont allumés.
– Tourner le bouton de réglage lentement vers la
droite jusqu’à ce que le relais de la réglette de
prises commute et alimente les appareils Slave
en courant.
– Contre-test : éteindre l’appareil Master. Les ap-
pareils Slave doivent s’arrêter automatiquement.
– Si les appareils Slave ne s’éteignent pas après
la coupure du Master : relever le seuil de com-
mutation.
– Mettre en marche l’appareil Master et l’éteindre
lorsque les appareils Slave sont activés.
– Tourner le bouton de réglage lentement vers
la gauche jusqu’à ce que le relais de la réglette
de prise coupe et n’alimente plus les appareils
Slave en courant.
Technische Daten
Technical data
Caractéristiques techniques