Vertiv™ eSure™ Power Extend Converter Mounting Bracket, Door, and Top Cover Kits Installation Manual
16
Table 8 Spacing and Power Restrictions: Spec. No. 582136800 List 12 Operating in a Vertiv™ OSP Cabinet Spec. No. F2010398
Distribution Row
Watts Per Power Extend Converter
No Spaces
1 Pole / Space
2 Pole / Space
3 Pole / Space
4 Pole / Space
Row 1 Only
300 W
800 W
600 W
475 W
400 W
Note: Row 1 is the Bottom Row
2.3
Preparing the Distribution Cabinet
Procedure
[ ] 1.
If the power extend converter is to be installed for a newly connected load, connect the load and load return cables for
the distribution position to be occupied by the power extend converter. At the same time, connect the power extend
converter return wire faston tab (P/N 565990) provided with the power extend converter to the cabinet’s return busbar
(use the same location as the return lead to the load). At the same time (if required), connect the separately ordered
power extend converter paralleling busbar (P/N 60016097 for paralleling two converters, P/N 545346 for paralleling
three converters) to the distribution panel load busbars (use the same location as the load lead to the load). See Figure
12 and Figure 13. Torque as indicated in Figure 12 and Figure 13.
[ ] 2.
If the power extend converter is to replace an existing circuit breaker, remove the circuit breaker and verify the load and
return cables for the position are wired and labeled correctly. At the same time, connect the power extend converter
return wire faston tab (P/N 565990) provided with the power extend converter to the cabinet’s return busbar (use the
same location as the return lead to the load). At the same time (if required), connect the separately ordered power
extend converter paralleling busbar (P/N 60016097 for paralleling two converters, P/N 545346 for paralleling three
converters) to the distribution panel load busbars (use the same location as the load lead to the load). See Figure 12 and
Figure 13. Torque as shown Figure 12 and Figure 13.
NOTE!
The return wire faston tab (P/N 565990) may be connected to either the top or bottom return bar in a 2- row cabinet.