Vertiv™ eSure™ Power Extend Converter Mounting Bracket, Door, and Top Cover Kits Installation Manual
24
[ ] 3.
Ensure the enable/disable switch on the power extend converter is in the disable (down) position. See Figure 16.
Repeat for each power extend converter to be installed.
Figure 16 Enable/Disable Switch
[ ] 4.
Connect the return wire (P/N 564330) to a power extend converter. Plug the power extend converter into the
distribution panel. Note: Orient the white square on the return wire faston receptacle’s locking tab as shown in Figure
17. Secure the power extend converter to the mounting bracket with the screw provided with the power extend
converter. See Figure 17. Torque as shown in Figure 17. Repeat for each power extend converter to be installed.
[ ] 5.
Place the enable/disable switch on the power extend converter to the enable position. See Figure 16 on page 24. If two
or three power extend converters are connected in parallel to a load that exceeds 1000 watts peak, they should be
switched on simultaneously.
[ ] 6.
Observe the status of the power extend converter front panel local indicator. If operating normally, this indicator should
be illuminated green. See Figure 16 on page 24.
[ ] 7.
Ensure that there are no local or remote alarms active on the power system.
[ ] 8.
Enable the external alarms or notify appropriate personnel that this procedure is finished.
Status Indicator
Enable / Disable Switch
Output Voltage Test Points
Enable
Disable
Vout+
Vout-
Ensure the enable/disable switch
on the power extend converter is
in the disable (down) position
before installing.